4 mechanical considerations, 1 positioning the liebert xdp, Figure 8 dimensions – Liebert Refrigerant Distribution Unit XDP User Manual

Page 11: Table 1 liebert xdp dimensions, Mechanical considerations, Positioning the liebert xdp, Figure 8, Dimensions, Table 1, Liebert xdp dimensions

Advertising
background image

Product Description

5

1.4

Mechanical Considerations

1.4.1 Positioning the Liebert XDP

Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at

least 3 feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.
For additional technical information, refer to the System Design and Configuration Document for the

Liebert XD

System, SL-16655. The document is available in electronic format at Liebert’s Web site,

www.liebert.com

, as well as from your local Emerson Network Power representative.

Figure 8

Dimensions

Table 1

Liebert XDP dimensions

Model

50/60Hz

Dimensional Data inches (mm)

Shipping Weight, lb (kg)

A

B*

C

D

E

Domestic

Export

XDP160

38 (965)

34 (864)

33-1/8 (841)

33 (838)

36 (914)

990 (449)

1067 (484)

* The dimension does not include the bezel of the disconnect switch.

Unit Dimensional Data

Floor Cutout Dimensions

E

D

A

Overall

C

Side Panel

B

Overall

DPN000767
Pg. 2, Rev. 6

D

Unit Base

E

Unit Base

78"

(1981mm)

11"

(279mm)

5" (127mm

)

1" (25mm)

5-1/2"

(140mm)

The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.