2 setpoints, Min temp sp, High cw temp – Liebert Refrigerant Distribution Unit XDP User Manual

Page 28: Hi air temp, Low air temp, 3 status, 4 active alarms, 5 alarm history, Setpoints, Status

Advertising
background image

Microprocessor Control

22

4.3.2 SETPOINTS

Selecting SETPOINTS from the Main Menu will reveal the following menu items:

MIN TEMP SP

Minimum Room Temperature Setpoint—This is used to keep the room temperature above the set-

point. The Liebert XDP can lower the room temperature too much depending on the room dew point

and load. This setpoint will back off the cooling to keep the room temperature above this temperature.

HIGH CW TEMP

High Chilled Water Temperature Setpoint—There could be many reasons that the chilled water tem-

perature is above this setpoint (e.g., chiller problem, control valve failure, etc.) This is the setpoint at

which the HIGH CW TEMP alarm will be activated.

HI AIR TEMP

High Room Air Temperature Setpoint—This is the setpoint at which the HIGH REMOTE TEMP and

HIGH LOCAL TEMP alarms will be activated.

LOW AIR TEMP

Low Room Air Temperature Setpoint—This is the setpoint at which the LOW REMOTE TEMP and

LOW LOCAL TEMP alarms will be activated.

4.3.3 STATUS

The user can check the status of the control valve, pump operation, and refrigerant and chilled water

temperature.

CONTROL VALVE—0-100%
PUMP 1—On/Off
PUMP 2—On/Off
REFRIG T—Refrigerant temperature 0-100° F
CW TEMP—Chilled Water temperature 0-100° F

4.3.4 ACTIVE ALARMS

This submenu allows the user to review any present alarms. If no alarms are present, the screen will read

“No Alarms Present.” If any alarms are occurring, the screen will display “Alarm XX of YY,” followed by

the alarm text (“XX” is the reference number of the alarm shown, “YY” is the total number of alarms).
If more than one alarm is present, use the Up or Down arrow keys to scroll through the alarms.

4.3.5 ALARM HISTORY

This submenu allows the user to review the 60 most-recent alarms. The first line of the screen will

show the alarm number—01 being the newest—and the name of the alarm. The second line of the

screen will show the most recent alarm’s date and the time in 24 hour format. Use the Up or Down

arrow key to scroll through the alarm history list.

Table 13

Setpoint functions, default values and allowable ranges

Menu Item

Function

Default, °F (°C)

Range, °F (°C)

MIN TEMP SP

Minimum room temperature setpoint

72 (22)

50-80 (10-27)

HI CW TEMP

High chilled water temperature setpoint

55 (13)

35 to 95 (2-35)

HI AIR TEMP

High room air temperature setpoint

80 (27)

35 to 95 (2-35)

LO AIR TEMP

Low room air temperature setpoint

65 (18)

35 to 95 (2-35)

* For optimal cooling performance, the minimum temperature setpoint should be at least 1-2° below the expected temperature at

the remote sensor, which may require additional consideration of the remote sensor location or minimum temperature setting. If
the minimum temperature setpoint is set above the typical remote temperature sensor reading, this will reduce the Liebert XD
cooling output and, in extreme cases, cause erratic Liebert XD performance.

NOTE
This is not a true room temperature setpoint. The Liebert XDP has no heaters; it will try to cool

as much as possible. If it is able to cool the room to this setpoint, it will back off its cooling

capability to try to keep the room temperature at or above this setpoint.

Advertising