Figure 9 piping access points, Figure 9, Piping access points – Liebert Refrigerant Distribution Unit XDP User Manual

Page 12: Table 2, Unit piping outlet connection sizes, inches, od cu

Advertising
background image

Product Description

6

Figure 9

Piping access points

Table 2

Unit piping outlet connection sizes, inches, OD Cu

Model

Pipe Connection Point

50/60 Hz

A

B

C

D

XDP160

2-1/8 1-1/8

2-5/8

2-5/8

Dimensions are
approximate
and subject to change
without notice.

16-1/8"

(410mm)

17-1/4"

(438mm)

10" (254mm)

19"

(483mm)

A - Return From Cooling Modules

B - Supply to Cooling Modules

D - Chilled Water Return
To Chilled Water Source

C - Chilled Water Supply
From Chilled Water Source

* Allow 8" (204mm) clearance for filter replacement.
** To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly

between the discharge line of the Liebert XDP and the first bypass flow controller
or the first cooling module.

DPN000767
Pg. 3, Rev. 6

Install replaceable filter dryer assembly
in liquid supply line B.

To first cooling module
or bypass flow controller **

* Orientation
determined
by installer.