0 alarm descriptions and solutions, 1 alarm descriptions, Larm – Liebert Refrigerant Distribution Unit XDP User Manual

Page 34: Escriptions, Olutions, Alarm descriptions

Advertising
background image

Alarm Descriptions and Solutions

28

5.0

A

LARM

D

ESCRIPTIONS

AND

S

OLUTIONS

5.1

Alarm Descriptions

LOSS OF FLOW P1—Activated when Pump 1 is commanded to run and the differential pres-

sure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting

to start Pump 1 for 120 seconds (including time delays), the Liebert XDP will automatically

switch to the other pump to establish flow.

LOSS OF FLOW P2—Activated when Pump 2 is commanded to run and the differential pres-

sure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting

to start Pump 2 for 120 seconds (including time delays), the Liebert XDP will automatically

switch to the other pump to establish flow.

SHORT CYCLE—Activated when the Liebert XDP is trying to establish flow (differential pres-

sure), and it is unable to do it. The Liebert XDP will attempt to establish flow for 4 minutes on

each pump, for a total of 8 minutes. If this “cycling” occurs within 30 minutes and the Liebert

XDP still does not establish flow, a SHORT CYCLE alarm will be present. This alarm will shut

down the Liebert XDP. Main power (disconnect switch) must be turned Off, then back On to clear

this alarm. The cycling time for the SHORT CYCLE alarm can be adjusted from the default of 30

minutes; the range is from 10 minutes to 60 minutes.

CONDENSATION!—Activated when water is detected at the Liebert XD cooling module (24VAC

is applied to the condensation input on the control). When this alarm is active, the control will

raise its refrigerant control point by 4°F (-16°C). Alarm will reset when the 24VAC signal ends or

main power is removed.

VALVE FAILURE—Activated when the chilled water control valve has been commanded by the

control to open or close and no change is detected from the valve-position signal. The control will

close the valve and then try to control the control valve based on its travel time. Main power (dis-

connect switch) must be turned Off, then back On to clear this alarm.

CUSTOMER ALRM—Activated when 24VAC signal is applied to the customer alarm input on

the control board. Alarm will reset when the 24VAC signal is taken away.

HIGH CW TEMP—Activated when entering chilled water temperature exceeds the user speci-

fied setpoint. The alarm will reset itself when the entering chilled water temperature drops below

the setpoint.

FAILED CW SENSOR—Activated when the control stops receiving a signal from the entering

chilled water temperature sensor. The alarm will reset itself when the temperature sensor signal

is re-established.

HIGH REMOTE TEMP & HIGH LOCAL TEMP—Activated when the remote or local temper-

ature exceeds the user specified setpoint. The alarm will reset itself when the room temperature

drops below the setpoint.

LOW REMOTE TEMP & LOW LOCAL TEMP—Activated when the remote or local tempera-

ture is below the user-specified setpoint. The alarm will reset itself when the room temperature

raises above the setpoint.

REMOTE SENS PROB—Activated when no signal is present from the remote temperature or

humidity sensors. Alarm will reset when the temperature and humidity signals are re-estab-

lished.

LOCAL SENS PROB—Activated when no signal is present from the local temperature or

humidity sensors or when communication with the display is lost. The alarm will reset when the

temperature and humidity signals are re-established.

HIGH REFRIG TEMP—Activated when the refrigerant temperature exceeds the user-specified

setpoint. The alarm will reset itself when the refrigerant temperature drops below the setpoint.

LOW REFRIG TEMP—Activated when the refrigerant temperature drops 1.5°F (1°C) below the

refrigerant temperature control point. The alarm will reset itself if the refrigerant temperature

rises before the control shuts down because of low refrigerant temperature.

NOTE
Alarms must be acknowledged before they can be reset. To acknowledge or silence an alarm,

press the ALARM SILENCE / ? key.

Advertising