Troubleshooting

31

6.0

T

ROUBLESHOOTING

Table 16

Troubleshooting the XDP

Symptom

Possible Cause

Check or Remedy

Pump will not energize

No main power

Check L1, L2 and L3 for rated voltage.

Loose electrical connections

Tighten connections.

Overloads tripped

Allow pump to cool. Check amp draw.

Tripped circuit breaker

Check circuit breaker to pump(s).

Incorrect phase wiring

See Table 5.

Pump will not run

No chilled water

Check and verify that there is supply chilled water to the

Liebert XDP.

Isolation valve(s) on pump suction

and/or discharge is closed.

Open all isolation valves completely during normal

operation.

Supply chilled water is too high

Check and verify that the chilled water temperature

setpoint is at 50°F (10°C) or lower and that there is flow

on the chilled water side.

Liebert XD cooling modules are Off

Check Liebert XD cooling module to make sure that they

are On prior to starting the Liebert XDP.

Low Refrigerant Temperature (high

dew point)

Check alarm(s) history on Liebert XDP. The Liebert XDP

was operating below the dew point for a significant

amount of time. Check humidity in conditioned space,

lower humidity if necessary to allow Liebert XDP to

operate at a lower temperature. (Disconnect must be

switched to Off then back On to allow Liebert XDP to

reset itself).

Incorrect location of

temperature-humidity sensors

Place the sensor on the RETURN AIR side of the primary

air mover (e.g., Liebert Deluxe System 3). Do not install

the sensor near unsealed doors, windows and similar

areas.

Pressure switch not making contact

Check both differential pressure settings. If not within

6 psi, ±1 psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then

manually change accordingly.

Not enough charge

See 3.0 - Checklist for Liebert XDP Startup.

Pump noisy

Cavitation due to vapor in pump

Check for adequate charge in system, refer to the User's

Manual. 3.0 - Checklist for Liebert XDP Startup

Worn motor bearings

Replace pump

Liebert XDP (Pump)

suddenly stops

Low Refrigerant Temperature (High

dew point)

Check humidity of room along with location of remote

sensors. Make sure that the sensors are not located in a

cold area where there is a lack of sufficient air flow.

Clogged filter/dryer and/or impeller

Clean out debris.

Pipe rattle

Loose pipe connections

Check pipe connections

Chilled water valve not

working

Motor operates but valve won't open

Check linkage for adjustment and be sure that it is tight on

the valve.

Actuator motors

No 24 VAC power to motor

Check for 24 VAC between P2-1 and P2-4.

No signal from control

Check 24 VAC at P22-1 (close) or P22-3 (open).

Motor not operating

Unplug P22 completely off of the board. Jumper P22-5 to

P2-4 for grounding, then jumper P22-1 to P2-1 to drive

close. Remove jumper to close, and then jumper P22-3 to

P2-1 to drive open. If motor fails to work, replace it.

Motor burnout

Check control panel for welded

contactor contacts or welded

overload contacts

Replace defective components.

Main 24 VAC fuse trips

Shorts or loose connections

Check the wiring connections of the 24 VAC circuit.

Faulty circuit board

Replace the circuit board.

Unstable pump

operation

R-134a pump loop is overcharged

While pump is running R-134a receiver level must be

within recommended levels (see Figure 21).