Figure 12 high voltage connections—60hz – Liebert Refrigerant Distribution Unit XDP User Manual

Page 14

Advertising
background image

Product Description

8

2. Determine which knockouts in the electrical enclosure will be used and remove them (see

Figure 11).

Figure 11 Electrical enclosure knockout locations for field wiring

3. Route the input hazardous voltage electrical power wiring through the top left knockout (see

Figure 11) to the disconnect switch L1, L2 and L3 (see Figures 12 and 13). Observe proper

phasing.

4. Connect the ground wire to the ground lug (see Figures 12 and 13), which is in the middle left of

the enclosure.

Figure 12 High voltage connections—60Hz

Liebert XD Module Condensate
Connections (optional;
depends on features
supplied with Liebert XD Module)

User Interface
(Wall Box) Wiring

Temperature/Humidity
Sensor Wiring

Alternate Knockout
for Temperature/Humidity
Sensor Wiring

Enclosure Cover Not Shown for Clarity

Customer Power
Connection

Ground Lug

Disconnect Switch

Control
Fuse Blocks

Power Block

Pump Fuse
Blocks

Pump Contactors

Transformer 1

Transformer 2