6 time, 7 date, 8 setup operation – Liebert Refrigerant Distribution Unit XDP User Manual

Page 29: Restart time delay, C/f degrees, Pump start td, Time, Date, Setup operation, Table 14

Advertising
background image

Microprocessor Control

23

4.3.6 TIME

To change the time, press ENTER to select the function, then use the Up or Down arrow key to

change the first character, press ENTER to store, then press the Up or Down arrow key to change the

second character, press ENTER to store, etc.

4.3.7 DATE

To change the date, press ENTER, then use the Up or Down arrow key to change the first character,

press ENTER to store, press the Up or Down arrow key to change the second character, etc.

4.3.8 SETUP OPERATION

Selecting Setpoint/Setup from the Main Menu will display the following selections:

Use the Up and Down arrow keys to scroll through the submenu, then press the ENTER button to access

a function. To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.

RESTART TIME DELAY

This function specifies the time for the unit to restart after main power is restored to the unit. If sev-

eral systems are operating, the time delays should be set to different values to cause a sequential

start. Delay can be set from 0.1 minutes (6 seconds) to 9.9 minutes. Setting the value to “NO!” will

prevent the unit from restarting when power is restored. In this case, the unit must be restarted man-

ually by pressing the “On/Off” key.
To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.

C/F DEGREES

The control can be selected to show readings and setpoints in either degrees Fahrenheit (F) or

Celsius (C). To make changes or review the setting, see 4.3.1 - Viewing or Changing Settings.

PUMP START TD

The user may set a pump start time delay (in seconds) to ensure that refrigerant begins flowing when

the pump starts. If refrigerant does not begin flowing before this delay expires, the pump will stop for

a period that the user may also specify (see PUMP OFF TD). After this delay, the pump will again

begin its startup sequence.
To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.

NOTE
The clock uses the 24-hour system (for example, 17:00 would be 5:00 PM). The date and time

are kept current even when the control board is not powered.

NOTE
None of these setpoints should be changed before consulting an Emerson Network Power

representative. Changing any of these setpoints could drastically affect the system.

Table 14

Setup operation functions default values and allowable ranges.

Menu Item

Function

Default

Range

RESTART

Restart time delay

0.1 min

0 to 9.9 min

(0 = manual restart)

C/F DEGREES

Celsius or Fahrenheit

F

C or F

PUMP START TD

Pump start time delay

10 sec

3 - 120 sec

PUMP WAIT TD

Pump wait time delay

10 sec

3 - 120 sec

PUMP OFF TD

Pump off time delay

5 sec

5 - 120 sec

LEAD PUMP

Lead Pump

Pump 1

Pump 1 / Pump 2

DIPSWCH

DIP switch status

NA

NA

VALVE TIME

Control valve travel time

60 sec

50 - 250 sec

NOTE
Setpoints and system setup parameters are kept in non-volatile memory.

Advertising