Microprocessor Control

26

Change Password—SERVICE PASSWORD

The factory default SERVICE PASSWORD is “123”—this password protects setup operations and

more-critical alarm settings. To change the SERVICE PASSWORD:
1. Press the MENU key to display the Main Menu.
2. Use the Up or Down arrow key to scroll to the SERVICE PASSWORD function.
3. Press ENTER to access the SERVICE PASSWORD function. The LCD will display three zeros (000).
4. Enter the present, three-digit password.

a. Use the Up or Down arrow key to enter the first number.
b. Press the ENTER button to select the second number in the password.
c. Use the Up or Down arrow key to enter the second number.
d. Enter the third number by repeating Steps b and c.
e. Press the ENTER button to accept the password. The LCD will display the message

PASSWORD OK.

5. Press the ENTER button; the LCD displays the message ENTER NEW PSW and the current

password. The first numeral will be selected.

6. Use the Up or Down arrow key to enter the first number of the new password. Press the ENTER

button to select the second numeral in the password.

7. Use the Up or Down arrow key to enter the second number of the new password. Press the

ENTER button to select the third numeral in the password.

8. Use the Up or Down arrow key to enter the third number of the new password. Press the ENTER

button to save the new password.

4.3.10 CALIBRATE SENSOR

The local and the remote temperature and humidity sensors can be calibrated by selecting this menu

item. The temperature sensor can be calibrated ± 5°F and the humidity sensor can be calibrated

±10% RH. To prevent coil condensation that could damage the Liebert XDP, the sensors must be cali-

brated to a known source.

4.3.11 ALARM ENABLE

Some alarms can be disabled or enabled as part of the user’s customized setup. An alarm that has

been disabled will not report to the wall box beeper nor to the common alarm relay. Alarms are

enabled by default.
Use the Up or Down arrow key to select a particular alarm; “YES” enables the alarm, “NO” disables

the alarm. Press ENTER to save the change.

4.3.12 ALARM TIME DELAY

Some alarms can be programmed with a time delay as a means of preventing nuisance alarms. This

function specifies the amount of time an alarm must be present before the Liebert XDP recognizes

and annunciates the alarm. If the alarm condition goes away before the time delay has expired, the

alarm will not be recognized, and the time delay timer will be reset.

4.3.13 COM ALARM ENABLE

Each individual alarm can be selected to energize or not to energize the common alarm relay. If the

energize common alarm function is set to YES, the relay is energized immediately as the alarm is

annunciated and de-energized when the alarm condition goes away (only after the alarm has been

recognized). If the alarm is completely DISABLED, the alarm has no effect on the common alarm

relay.
Use the Up or Down arrow key to scroll to a particular alarm, press the ENTER button to select it,

then press the ENTER button to change the state (Yes or No).