Lincoln Impinger X2 Ovens with Push Button Controls 3240-2 User Manual

Page 13

Advertising
background image

Impinger X2 – Analog Service Manual – Dom & Int’l

13

Burner control

Check for supply voltage at terminal #7 on burner

control. If no voltage is present, trace wiring back to air

pressure switch. If voltage is present, check for output

voltage (after the 30 second delay) from terminal #8 on

the burner control. If there is no output voltage from

terminal #8, (after the 30 second delay) replace the

burner control. If there is output voltage, proceed.

Pilot valve

Check for supply voltage to pilot valve. If no voltage is

present, trace wiring back to burner control. If voltage is

present, check for gas pressure at the pilot line

connection. If no gas pressure is present during

ignition, check for any blockage in the assembly. If

there are no obstructions, and there is gas supplied to

the oven, replace the gas valve.

Burner control

Check to see that the high voltage igniter circuit on the

burner control is energized. To check, turn power off,

disconnect the igniter lead from the burner control. Turn

power on. If no spark is visible, replace burner control.

If a spark is visible at burner control, proceed.

Burner igniter

Check the burner igniter head for any damage or

obstructions also check for frayed or broken wire.

Check spark gap, gap should be 3/32” If there is visible

damage, replace burner igniter.

No pilot flame

If there is supply voltage to the burner control, and the

pilot valve and igniter circuits are energized, visually

check for a pilot flame. This may be done by looking

through the inspection view port on the end of the

burner. If no pilot flame is visible, check the pilot tube.

Pilot tube

Check for gas pressure at the pilot tube. Disconnect

pilot tube at the burner and connect manometer to pilot

tube. If no gas pressure is present during ignition,

check for blockage of the pilot tube. If the pilot tube is

clear, proceed.

Pilot orifice

If there is gas pressure at the pilot tube, check the pilot

orifice for blockage or obstructions. Replace pilot orifice

as needed.

Burner igniter

Check the burner igniter head for any damage or

obstructions also check for frayed or broken wire.

Check spark gap, gap should be 3/32” If there is visible

damage, replace burner igniter.

Flame sensor

(There should be a visible pilot flame at this time.)

To check for proper flame sensor operation, connect a

digital multimeter (capable of measuring D.C. micro

amps) in series between the flame sensor wire

(normally connected to terminal #13 on the burner

control) and terminal #13 on the burner control. With a

visible pilot flame, the current reading should be 0.7

micro amp minimum. NOTE: The D.C. micro amp test

must be conducted with the oven in low flame operation

only. If these values are not achieved, replace flame

sensor. Also check for any type of damage to flame

sensor wire and connections.

Power supply

If there is a pilot flame, and there is sufficient micro

amp. current, but the flame will not stay on, check for

proper polarity of the power supply.

Burner control

If there is sufficient micro amp current, and there is

proper polarity of the power supply, but the burner will

not stay on, check the reset button for the burner

control. If the reset switch checks okay, replace the

burner control.

Pilot flame, but no main flame

NOTE: Flame should be

Check for supply voltage to electronic temperature

Advertising