Lincoln Impinger X2 Ovens with Push Button Controls 3240-2 User Manual

Page 6

Advertising
background image

Impinger X2 – Analog Service Manual – Dom & Int’l

6

TROUBLESHOOTING GUIDE

3240-2*

120/230VAC

60 HZ.

1 PHASE

3240-2*

120/230VAC

60 HZ.

3 PHASE

3262-2*

120/230VAC

60 HZ.

1 PHASE

3262-2*

120/230VAC

60 HZ.

3 PHASE

3270-2*

120/230VAC

60 HZ.

1 PHASE

3270-2*

120/230VAC

60 HZ.

3 PHASE

*NOTE:

Model number ending in TS indicates top belt is split belt

Model number ending in SB indicates bottom belt is split belt

Model number ending in SS indicates both belts are split belts

SYMPTOM

POSSIBLE CAUSE

EVALUATION

Oven fan will not run

Incoming power supply

Check circuit breakers. Reset if required. Call power

co. if needed.

Fuse, 2 Amp, control (F7)

Check, replace if necessary.

Fuse holder

Check, replace if necessary.

Switch, oven fan

Check continuity between switch terminals. Replace

switch as needed.

30 minute time delay relay

Check for supply voltage to 30 minute time delay relay

at terminals #2 and #3. If no voltage is present, trace

wiring back to main power switch. If there is supply

voltage at terminals #2 and #3, check for output voltage

at terminals #1 and #3. If there is incoming voltage but

no output voltage, and the main power switch is on,

replace the 30 minute time delay relay.

Relay, main fan

Check for supply voltage to relay contacts, if no voltage

is present, trace wiring back to power supply. Check for

120VAC to the coil of the main fan relay. If no voltage is

present, trace wiring back to the 30 minute time delay

relay, check to be sure that the Overload Protector

contacts are closed. If contacts are open, see

“Overload Protector” below. If voltage is present, check

to insure relay contacts are closing. Replace relay as

needed.

Overload protector, main fan

Check to be sure overload contacts are closed. If not

closed, re-set overload. If contacts do not close,

replace overload protector. If contacts close, test for

proper operation. If the overload contacts do not stay

closed, and the amperage is below the overload

setting, replace the overload protector.

3240 should be set at 13A

3260 should be set at 18A

3270 should be set at 18A

Main fan motor

Check for supply voltage at motor. If no voltage is

present, trace wiring back to the overload protector.

WITH POWER OFF: Check for opens, shorts or

grounds. Turn motor shaft to check for locked rotor.

Capacitor

Check for shorts or grounds.

WARNING: Capacitor has a stored charge, discharge

before testing.

Drive belt

Check for loose or broken drive belt. Adjust motor for

proper belt tension (maximum of 3/8-inch deflection), or

replace drive belt as needed.

Bearings, Fan shaft

Check for any damage or excessive wear on the shaft

Advertising