Vertical Vent Installation

Important Notes

1. All vertically terminated vent installations use 6-5/8”x 4”

Security™ Secure Vent™ pipe*.

2. If the vent passes through a ceiling or floor, a firestop

- Simpson #963 or Security™ #SV4BF - is required.

3. If the vent passes through the roof, a roof flashing - Simp-

son #943 or 943S or Security™ #SV4FA or SV4FB - and

storm collar - Simpson #953 or Security™ #SV4FC - are

required.

4. A 1-inch clearance from the vent pipe to combustible

materials must be maintained.

5. A maximum of either two 45º elbows or two 90º elbows

may be used. See Page 16 for allowable offsets.

6. The maximum system height is 30 feet (9.1M) and the

minimum is 10 feet (3M).

Flue Restrictors

This stove requires a balanced flue to ensure proper com-

bustion. As such, flue restrictors may need to be installed

depending on the vent configuration of your stove. The

drawings on the next page show all the allowable pipe con-

figurations for the Epic™ gas stove. To properly install the

flue restrictors, find your pipe configuration in the drawings

on the next page and note which restrictor setting is recom-

mended. The flue restrictors are shipped in the firebox of

your stove. Install the flue restrictors using the four allen

head screws according to the diagram below. Install the

flue restrictor screws in their original holes in the top of

the firebox. Restrictor positions are based on tests run in

a laboratory.

A

B

C

D

* Other approved chimney brand is Simpson Dura-Vent DV-GS.

Storm Collar

Vertical Termination Cap

Ceiling Firestop

Ceiling Minimum

Framing 10”x 10”

Roof - Maintain

1” Clearance

to Combustibles

Pipe Length

Flashing

Figure 23