Output Voltage Selection
The Output Voltage is user configurable, and is designed to allow select-
ing or changing the desired output voltage to match the utility via the
GXT2 Configuration Program provided with the UPS. The settings to
choose from are 100, 110, 115, 120, and 127 VAC output. The factory
default setting is 120 VAC.

!

CAUTION
Never change the voltage settings while the UPS is ON

and powering connected loads.
NOTE
Setting output voltage to 100 VAC will cause the UPS unit to

be derated (700/1000 VA to 90%, 1500/2000/3000 VA to

80%) of the VA and Watt ratings listed in the Specifications

section.