The UPStation GXT 2U UPS contains a standard DB-9 serial port female
connector located on the rear of the UPS unit. Several signals are pro-
vided on this port and are assigned as follows:

*Maximum voltage and current on pins 1, 7, 8, and 9 is 60V DC; 10.0 mA.

P

IN

4 - R

EMOTE

S

HUTDOWN

ON

B

ATTERY

1. This pin is functional only when the UPS is in battery mode. If the

UPS is being powered by the utility, Pin 4 will ignore any signal on this
pin.

2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes

form the serial port using Liebert’s contact closure cable. It cannot be
used with just a contact closure unless the relay is used to switch a
voltage source. A 5-12 VDC signal for 1.5 seconds or greater is
required to signal a shutdown. Signals for less than 1.5 seconds will
be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds,
the command cannot be canceled.

Pin

Assignment Description

1

Low Battery (open collector)

2

UPS TxD (typical RS-232 levels)

3

UPS RxD (typical RS-232 levels)

4

Remote Shutdown (5-12VDC, 10-24 mA max); battery operation

5

Common

6

Remote Shutdown (short to pin 5); all modes of operation

7

Low Battery (open emitter)

8

Utility Fail (open emitter)

9

Utility Fail (open collector)

Pin Assignment

Collector to Emitter*

5

4

3

2

1

6

7

8

9

(-)

(+)

330 Ohms

Open
Collector

Open
Emitter