Troubleshooting guide (continued) – Liebert UPSTATION GXT 2U User Manual

Page 30

Advertising
background image

26

AC LED is flashing. UPS detected a line-to-

neutral reversal or a loss

of proper grounding;

continuous horn and

UPS will not start.This is

active only when power

is first applied to the

input. Once the UPS is

running, the AC LED will

not start flashing, even if

the input wiring is

changed.

Contact a qualified electrician to

verify site wiring.

Battery LED is

flashing.

Battery source is not

available; continuous

horn.

Check battery connections,

completely power down and

restart UPS.

NOTE: If the battery circuit

opens while the UPS is running,

it will be detected when the next

battery test is performed.

Bypass LED is

flashing.

Bypass voltage is

present, but is disabled

for use because the

voltage or frequency is

outside acceptable limits.

The AC input powers the PFC

input and serves as the bypass

source. If the AC is present but

the voltage or frequency

exceeds the acceptable range

for safe operation with a load,

the bypass will be disabled and

this LED will flash, indicating that

the bypass is unavailable.

Troubleshooting Guide (Continued)

Problem

Cause

Solution