Specifications (continued) – Liebert UPSTATION GXT 2U User Manual

Page 33

Advertising
background image

29

SPECIFICATIONS (CONTINUED)

Model Number

GXT2-2000RT120

GXT2-3000RT120

Model Rating

2000VA / 1400W

3000VA / 2100W

DIMENSIONS in (mm)
Unit
W x D x H in. (mm)

3.5 x 21.5 x 17

(87 x 547 x 430)

3.5 x 24.2 x 17

(87 x 618 x 430)

Shipping
W x D x H in. (mm)

10.5 x 27.2 x 23

(268 x 692 x 585)

10.5 x 27.2 x 23

(268 x 692 x 585)

WEIGHT lbs (kg)
Unit

54 (24)

69 (31)

Shipping

62.6 (28.4)

78.0 (35.4)

INPUT AC PARAMETERS
Voltage Range
(typical)

120 VAC nominal; variable based on output load

100% - 90% loading

90 VAC / 140 VAC

90 VAC / 140 VAC

90% -70% loading

80 VAC / 140 VAC

80 VAC / 140 VAC

70% -30% loading

70 VAC / 140 VAC

70 VAC / 140 VAC

30% - 0% loading

60 VAC / 140 VAC

60 VAC / 140 VAC

Frequency

40 - 70 Hz; Auto Sensing

Input Power Cord

10 ft. attached

w/ NEMA 5-20 plug

10 ft. attached

w/ NEMA L5-30 plug

OUTPUT AC PARAMETERS

Output Receptacles

(4) 5-20R T-Slot,

accepts 15A plug

(4) NEMA 5-15R

(1) NEMA L5-30R on 12 in cord

Voltage

100/110/115/120/127 (user configurable) VAC; ±3%

Frequency

50 Hz or 60 Hz

Waveform

Sinewave

Main Mode
Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

BATTERY PARAMETERS
Type

Valve-regulated, nonspillable, flame retardant, lead acid

Qty x V x Rating

4 x 12V x 9.0 AH

6 x 12V x 9.0 AH

Battery Mfg / Part #

Panasonic / UP-VW1245P1

Yuasa / REW 45-12 FR

Back-up Time

See Battery Run Times charts

Recharge Time

5 hours to 95% capacity after full discharge into 100% load

ENVIRONMENTAL
Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000 m) maximum

Audible Noise

<55 dBA, at 1 meter from the rear

<50 dBA, at 1 meter from the front or sides

AGENCY
Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

RFI/EMI

FCC Part 15, Subpart B, Class A

Surge Immunity

IEEE/ANSI C62.41 Category A & B

Transportation

ISTA Procedure 1A

Advertising