Specifications, Pecifications – Liebert UPSTATION GXT 2U User Manual

Page 32

Advertising
background image

28

SPECIFICATIONS

Model Number

GXT2-700RT120

GXT2-1000RT120

GXT2-1500RT120

Model Rating

700VA / 490W

1000VA / 700W

1500VA / 1050W

DIMENSIONS in (mm)
Unit
W x D x H in. (mm)

3.5 x 21.5 x 17

(87 x 547 x 430)

3.5 x 21.5 x 17

(87 x 547 x 430)

3.5 x 21.5 x 17

(87 x 547 x 430)

Shipping
W x D x H in. (mm)

10.4 x 27.3 x 22.5

(268 x 692 x 585)

10.4 x 27.3 x 22.5

(268 x 692 x 585)

10.4 x 27.3 x 22.5

(268 x 692 x 585)

WEIGHT lbs (kg)
Unit

48.9 (22.2)

49.1 (22.3)

50.6 (23)

Shipping

57.7 (26.2)

57.9 (26.3)

59.5 (27)

INPUT AC PARAMETERS
Voltage Range
(typical)

120 VAC nominal; variable based on output load

100% - 90% loading

80 VAC / 140 VAC

80 VAC / 140 VAC

90 VAC / 140 VAC

90% -70% loading

80 VAC / 140 VAC

80 VAC / 140 VAC

80 VAC / 140 VAC

70% -30% loading

70 VAC / 140 VAC

70 VAC / 140 VAC

70 VAC / 140 VAC

30% - 0% loading

60 VAC / 140 VAC

60 VAC / 140 VAC

60 VAC / 140 VAC

Frequency

40 - 70 Hz; Auto Sensing

Input Power Cord

6 ft. attached

w/ NEMA 5-15 plug

10 ft. attached

w/ NEMA 5-15 plug

10 ft. attached

w/ NEMA 5-15 plug

OUTPUT AC PARAMETERS
Output Receptacles

(4) NEMA 5-15R

Voltage

100/110/115/120/127 (user configurable) VAC; ±3%

Frequency

50 Hz or 60 Hz

Waveform

Sinewave

Main Mode
Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

BATTERY PARAMETERS
Type

Valve-regulated, nonspillable, flame retardant, lead acid

Qty x V x Rating

4 x 12V x 7.0 or 7.2 AH

Battery Mfg / Part #

China Storage Battery / CSB FR 1270 F2

Back-up Time

See Battery Run Times charts

Recharge Time

5 Hours to 95% capacity after full discharge into 100% load

ENVIRONMENTAL
Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000m) maximum

Audible Noise

<50 dBA, at 1 meter from the rear

<45 dBA, at 1 meter from the front or sides

AGENCY
Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

RFI/EMI

FCC Part 15, Subpart B, Class A

Surge Immunity

IEEE/ANSI C62.41 Category A & B

Transportation

ISTA Procedure 1A

Advertising