25

Fault and Bypass

indicator LEDs and

diagnostic LED A

are illuminated.

UPS internal fan has a

problem or UPS

shutdown due to

temperature condition.

Load is on bypass power.

Ensure UPS is not overloaded,

ventilation openings not blocked,

or room ambient temperature is

not excessive. Wait 30 minutes

to allow UPS to cool, then restart

UPS. IF UPS does not restart,

contact your local dealer, Liebert

representative or the Liebert

Worldwide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED B

are illuminated.

UPS internal DC bus

overvoltage.

UPS requires service. Contact

your local dealer, Liebert

representative or the Liebert

Worldwide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED C

are illuminated.

UPS control power

supply fault.

UPS requires service. Contact

your local dealer, Liebert

representative or the Liebert

Worldwide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED D

are illuminated.

UPS PFC (Power Factor

Correction Circuit) fault.

UPS requires service. Contact

your local dealer, Liebert

representative or the Liebert

Worldwide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED E

are illuminated.

UPS inverter fault.

UPS requires service. Contact

your local dealer, Liebert

Representative or the Liebert

Worldwide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED A

and C are

illuminated.

UPS failed the battery

test.

Replace batteries. Contact your

local dealer, Liebert

representative or the Liebert

Worldwide Support Group.

Fault and Bypass

indicator LEDs and

diagnostic LED C

and E are

illuminated.

UPS shutdown due to a

command from the

communications port(s).

Your UPS has received a signal

or command from the attached

computer. If this was

inadvertent, ensure the

communication cable used is

correct for your system. For

assistance, contact your local

dealer, Liebert representative or

the Liebert Worldwide Support

Group.