Rs-232 communications protocol & command set – Panamax BANKS WIRING MB1000 User Manual

Page 12

Advertising
background image

10

RS-232 Communications Protocol & Command Set

SET AVR MODE

Sets AVR (Automatic Voltage Regulation) MODE.

Command:

!SET_AVR mode<CR>

mode = {OFF, STANDARD, SENSITIVE}

_________________________________________
If specified mode is invalid

Action:

No action will be taken, UPS will

request a valid mode setting

Response from UPS:

$INVALID_PARAMETER<CR>

$AVR = mode <CR>

_________________________________________
SET FEEDBACK MODE

Sets the feedback mode to ON (unsolicited) or OFF (polled).

When ON, a message will be sent to the controller every time the

status of an input (i.e. button), output (i.e. outlet) or power state

(i.e. overvoltage) changes.

If feedback is OFF, the controller must request status with a query

(see Queries section for more details).

Send to UPS:

!SET_FEEDBACK mode<CR>

mode = {ON, OFF}

_________________________________________
If specified mode is invalid

Action:

No action will be taken, UPS will

request a valid mode setting

Response from UPS:

$INVALID_PARAMETER<CR>

$FEEDBACK = mode<CR>

_________________________________________
SET LINEFEED MODE

With LINEFEED MODE set, a linefeed character (<LF>, 10d, 0Ah)

is appended to each response.

Send to UPS:

!SET_LINEFEED mode<CR>

mode = {ON, OFF}

_________________________________________

If specified mode is invalid

Action:

No action will be taken, UPS will

request a valid mode setting

Response from UPS:

$INVALID_PARAMETER<CR>

$LINEFEED = mode<CR>

_________________________________________

SET METER BRIGHTNESS

Sets the LCD display and outlet bank indicator brightness.

Send to UPS:

!SET_BRIGHT xxx<CR>

xxx = {100, 075, 050, 025}

_________________________________________
If specified brightness setting is invalid

Action:

No action will be taken, UPS will

request a valid brightness setting

Response from UPS:

$INVALID_PARAMETER<CR>

$BRIGHTNESS = xxx<CR>

_________________________________________
SET DISPLAY SCROLL MODE

Sets the LCD display SCROLL mode

Send to UPS:

!SET_SCROLLMODE xxx<CR>

xxx = {5SEC, 10SEC, OFF}

_________________________________________
If specified display scroll mode is invalid

Action:

No action will be taken, UPS will

request a valid mode setting

Response from UPS:

$INVALID_PARAMETER<CR>

$SCROLL_MODE = xxx<CR>

_________________________________________

SET DISPLAY SLEEP MODE

Sets the LCD display SLEEP mode

Command:

!SET_SLEEPMODE xxx<CR>

xxx = {30SEC, 60SEC, OFF}

If specified display sleep mode is invalid

Action:

No action will be taken, UPS will

request a valid mode setting

Response from UPS:

$INVALID_PARAMETER<CR>

$SLEEP_MODE = xxx<CR>

_________________________________________