Operating modes – Panamax BANKS WIRING MB1000 User Manual

Page 6

Advertising
background image

4

Operating Modes

Normal Operation (Utility Power) Mode

When connected to a live power source, the MB1000 provides

power and is ready to provide protection from under- and over-

voltages.

Rotate the navigation dial to scroll through the screens.

Automatic Voltage Regulation (AVR) Mode

Sensitive AVR: when receiving input voltages of 98 VAC – 135

VAC, the MB1000 supplies a regulated voltage of 120 VAC ± 5

VAC.

Standard AVR: when receiving input voltages of 93 VAC – 145

VAC, the MB1000 supplies a regulated voltage of 120 VAC ± 10

VAC.

OFF: AVR is disabled. No voltage correction.

UPS Mode

In the event of a loss of power to the unit, over-voltage, or

under-voltage, the MB1000 will function as a battery back-up. An

audible alarm will sound and the display will indicate the fault as

well as the number of minutes of battery life remaining.

Setup Mode

The setup menu allows the user to adjust several of the operating

parameters of the unit.

Please refer to diagram (page 5) for a detailed map of the menu

structure.

Setup Menu Navigation

Clockwise (CW) rotation of the navigation dial advances the

menu to the next item. If the menu is at the last item, SYSTEM

INFO, return to Normal Operation Mode.

Counter clockwise (CCW) rotation of the navigation dial sends

the menu to the previous item. If the menu is at the first item,

DISPLAY BRIGHTNESS, return to Normal Operation Mode.

Pressing the navigation dial selects the current menu item.

If there is no activity of the navigation dial for 60 seconds, the

menu will automatically return to Normal Operation Mode.

Parameter Selection and Adjustment

CW rotation of the navigation dial INCREASES the selected

parameter, or advances to the NEXT available value.

CCW rotation of the navigation dial DECREASES the selected

parameter, or goes back to the PREVIOUS value. Pressing the

navigation dial selects the current parameter value.

If there is no activity of the navigation dial for 60 seconds, return

to Normal Operation Mode.

If the BACK parameter is selected, return to the menu item selec-

tion.

Display Brightness

Display Brightness adjusts the brightness of the display back-

light.

Display Scroll Mode

If enabled, the display will automatically advance to the next

screen every 5 or 10 seconds.

Display Sleep Mode

With Display Sleep Mode enabled, the Display will go to the

lowest brightness setting (25%) after the designated time of

inactivity of the Navigation Dial {30 SEC, 60 SEC }.

The display will return to the set brightness level upon entering

Setup Mode, or UPS Mode.

FAULT

BATTERY: 15 MIN

UPS Mode Screen

120 VOLTS

NORMAL POWER

Normal Operation Screen

SETUP

Advertising