Important safety instructions, Fan module cooling requirements, Model 3511 dsus – Paradyne 3510 User Manual

Page 42

Advertising
background image

COMSPHERE 3500 Series Data Service Units

4-2

March 1999

3510-A2-GN32-60

Model 3511 DSUs

The Model 3511 DSU is designed for installation in a

COMSPHERE 3000 Series Carrier, which supplies
operating power and provides interfaces for connecting to
the digital network. Up to 16 DSUs can be installed in a
COMSPHERE 3000 Series Carrier. For installation of the
carrier, refer to the COMSPHERE 3000 Series Carrier,
Installation Manual
.

If installing additional units in a COMSPHERE

3000 Series Carrier that does not contain a fan module,
you may need to install one to dissipate heat. Use
Table 4-1 to determine if fan modules are necessary. This
table lists the fan module cooling requirements if your
carrier consists totally of Model 3511 DSUs. If your
carrier contains a mixture of circuit cards, see the
COMSPHERE 3000 Series Carrier, Installation Manual
for fan module cooling requirements and instructions for
installing the fan module.

Important Safety Instructions

Read and follow all warning notices and instructions

marked on the DSU or included in this guide.

If you have a standalone Model 3510 DSU, do not

attempt to service it yourself, as removal of the case will
expose you to dangerously high voltage points or other
risks. Refer all servicing to qualified personnel (see the

Equipment Warranty and Support

section in Chapter 1).

HANDLING PRECAUTIONS

FOR

STATIC-SENSITIVE DEVICES

This product is designed to protect
sensitive components from damage
due to electrostatic discharge (ESD)
during normal operation. When
performing installation procedures,
however, take proper static control
precautions to prevent damage to
equipment. If you are not sure of the
proper static control precautions,
contact your nearest sales or service
representative.

For additional safety instructions, see the

Important

Safety Instructions

section, Page B at the front of this

guide.

Table 4-1

Fan Module Cooling Requirements

Ambient

Temperat re

Number of Fan Modules Required

Temperature

Range

1 to 5 Carriers

6 Carriers

38 — 80

°

F

(33 — 26.7

°

C)

No fan module

1 fan module (place in second
carrier from top of cabinet)

80 —112

°

F

(26.6 — 44.5

°

C)

1 fan module per carrier

1 fan module per carrier