Chapter 4

Signal Connections

6023E/6024E/6025E User Manual

4-6

ni.com

PFI5/UPDATE*

DGND

Input

Output

PFI5/Update—as an input, this is one of the PFIs.

As an output, this is the UPDATE* (AO Update) signal. A
high-to-low edge on UPDATE* indicates that the analog
output primary group is being updated for the 6024E or
6025E.

PFI6/WFTRIG

DGND

Input

Output

PFI6/Waveform Trigger—as an input, this is one of the
PFIs.

As an output, this is the WFTRIG (AO Start Trigger) signal.
In timed analog output sequences, a low-to-high transition
indicates the initiation of the waveform generation.

PFI7/STARTSCAN

DGND

Input

Output

PFI7/Start of Scan—as an input, this is one of the PFIs.

As an output, this is the STARTSCAN (AI Scan Start)
signal. This pin pulses once at the start of each analog input
scan in the interval scan. A low-to-high transition indicates
the start of the scan.

PFI8/GPCTR0_SOURCE

DGND

Input

Output

PFI8/Counter 0 Source—as an input, this is one of the
PFIs.

As an output, this is the GPCTR0_SOURCE signal.
This signal reflects the actual source connected to the
general-purpose counter 0.

PFI9/GPCTR0_GATE

DGND

Input

Output

PFI9/Counter 0 Gate—as an input, this is one of the PFIs.

As an output, this is the GPCTR0_GATE signal. This signal
reflects the actual gate signal connected to the
general-purpose counter 0.

GPCTR0_OUT

DGND

Output

Counter 0 Output—this output is from the general-purpose
counter 0 output.

FREQ_OUT

DGND

Output

Frequency Output—this output is from the frequency
generator output.

*

Indicates that the signal is active low

1

Not available on the 6023E

2

Not available on the 6023E or 6024E

Table 4-2. I/O Connector Signal Descriptions (Continued)