Gpctr0_out signal, Gpctr0_up_down signal, Figure 4-37. gpctr0_out signal timing – National Instruments 6023E User Manual

Page 75: Gpctr0_out signal -45 gpctr0_up_down signal -45, Figure 4-36, Figure 4-37, Gpctr0_out signal timing -45

Advertising
background image

Chapter 4

Signal Connections

© National Instruments Corporation

4-45

6023E/6024E/6025E User Manual

Figure 4-36. GPCTR0_GATE Signal Timing in Edge-Detection Mode

GPCTR0_OUT Signal

This signal is available only as an output on the GPCTR0_OUT pin. The
GPCTR0_OUT signal reflects the terminal count (TC) of general-purpose
counter 0. You have two software-selectable output options—pulse on TC
and toggle output polarity on TC. The output polarity is software-selectable
for both options. This output is set to high impedance at startup.
Figure 4-37 shows the timing of the GPCTR0_OUT signal.

Figure 4-37. GPCTR0_OUT Signal Timing

GPCTR0_UP_DOWN Signal

This signal can be externally input on the DIO6 pin and is not available as
an output on the I/O connector. The general-purpose counter 0 counts down
when this pin is at a logic low and count up when it is at a logic high. You
can disable this input so that software can control the up-down
functionality and leave the DIO6 pin free for general use.

Rising-Edge

Polarity

Falling-Edge

Polarity

t

w

t

w

= 10 ns minimum

GPCTR0_SOURCE

GPCTR0_OUT

GPCTR0_OUT

(Toggle Output on TC)

(Pulse on TC)

TC

Advertising