Connecting the server to power

41

A qualified electrician must implement the single-point ground reference as
required among the power outlets of the CallPilot server, its associated
peripherals, and the power outlets of the switch.

Provide a sufficient number of properly grounded power outlets or power
bars for all equipment.

The single-point ground (SPG) required by the system can be an isolated
ground (IG) bus or AC equipment ground (ACEG) bus in the service
panel or transformer. The system must be connected to safety ground or
protective earth in accordance with NEC requirements. For international
use, the system must be connected to safety ground or protective earth in
accordance with Paragraph 2.5 of EN60950/IEC950.

Note: For a complete description of approved ground sources and
methods, seeCommunication Server 1000M and Meridian 1: Large
System Planning and Engineering
(NN43021-220). Insulated ground
wire must be used for system grounding.

Before you connect the server to the power source, review the following
diagram and the warning that follows to ensure that all peripheral hardware
devices are in place.

Nortel CallPilot

600r Server Hardware Installation

NN44200-307

01.03

Standard

5.0

14 May 2008