Install connector blocks on the backplane – National Instruments cFP-20xx User Manual

Page 13

Advertising
background image

© National Instruments Corporation

13

cFP-20xx Quick Start Guide

4. Install Connector Blocks on the Backplane

In order to connect I/O modules to input signals or to external loads, you need
to install a cFP-CB-x connector block or other connectivity accessory for each
I/O module on the backplane. Use the connector socket to the right of each I/O
module socket.

Caution

Do not insert or remove connector blocks or other connectivity

accessories while power is applied to them.

1. Wire field devices as described in

the I/O module and connector
block operating instructions.

Caution

Hazardous voltage

wiring should be performed
by qualified personnel and
in accordance with local
electrical standards.

2. Align the captive screws on the

connector block with the holes
on the backplane.

3. Press firmly to seat the connector block on the backplane.

4. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.)

length, tighten the captive screws to 1.1 N · m (10 lb · in.) of torque.

5. Repeat this procedure to install additional connector blocks on the backplane.

Advertising