Humidity ........................................... 10 to 90% RH, noncondensing

Maximum altitude............................. 2,000 m; at higher altitudes the isolation

voltage ratings must be lowered

Pollution Degree ............................... 2

Shock and Vibration

Operating vibration

Random (IEC 60068-2-64)......... 10–500 Hz, 5 g

rms

Sinusoidal (IEC 60068-2-6) ....... 10–500 Hz, 5 g

Operating shock
(IEC 60068-2-27).............................. 50 g, 3 ms half sine,

18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations

Safety

This product meets the requirements of the following standards of safety for
electrical equipment for measurement, control, and laboratory use:

IEC 61010-1, EN 61010-1

UL 61010-1, CSA 61010-1

For UL, hazardous location, and other safety certifications, refer to the product