Figure 37. retriggerable single pulse generation, Retriggerable single pulse generation – National Instruments Eight-slot USB Chassis NI cDAQ-9172 User Manual

Page 60

Advertising
background image

NI cDAQ-9172 User Guide and Specifications

60

ni.com

Figure 36 shows a generation of a pulse with a pulse delay of four and a
pulse width of three (using the rising edge of Source).

Figure 36. Single Pulse Generation with Start Trigger

Retriggerable Single Pulse Generation

The counter can output a single pulse in response to each pulse on a
hardware Start Trigger signal. The pulses appear on the Counter n Internal
Output signal of the counter.

You can route the Start Trigger signal to the Gate input of the counter. You
can specify a delay from the Start Trigger to the beginning of each pulse.
You also can specify the pulse width. The delay and pulse width are
measured in terms of a number of active edges of the Source input.

The counter ignores the Gate input while a pulse generation is in progress.
After the pulse generation is finished, the counter waits for another Start
Trigger signal to begin another pulse generation.

Figure 37 shows a generation of two pulses with a pulse delay of five and a
pulse width of three (using the rising edge of Source).

Figure 37. Retriggerable Single Pulse Generation

For information on connecting counter signals, refer to the

Default

Counter/Timer Routing

section.

SOURCE

GATE

(Start Trigger)

OUT

SOURCE

GATE

(Start Trigger)

OUT