Counter n source signal, Table 7. counter applications and counter n source, Table 8. counter n source timing – National Instruments Eight-slot USB Chassis NI cDAQ-9172 User Manual

Page 64: Routing a signal to counter n source

Advertising
background image

NI cDAQ-9172 User Guide and Specifications

64

ni.com

Counter n Source Signal

The selected edge of the Counter n Source signal increments and
decrements the counter value, depending upon the application the counter
is performing. Table 7 lists how this terminal is used in various
applications. Table 8 lists Counter n Source minimum pulse width.

Routing a Signal to Counter n Source

Each counter has independent input selectors for the Counter n Source
signal. You can route the following signals to the Counter n Source input:

80 MHz Timebase

20 MHz Timebase

100 kHz Timebase

Any PFI terminal

Analog Comparison Event

In addition, you can route Counter 1 TC or Counter 1 Gate to
Counter 0 Source. You can also route Counter 0 TC or Counter 0 Gate to
Counter 1 Source.

Table 7. Counter Applications and Counter n Source

Application

Purpose of Source Terminal

Pulse Generation

Counter Timebase

One Counter Time Measurements

Counter Timebase

Two Counter Time Measurements

Input Terminal

Nonbuffered Edge Counting

Input Terminal

Buffered Edge Counting

Input Terminal

Two-Edge Separation

Counter Timebase

Table 8. Counter n Source Timing

Description

Synchronization

Mode

Min (ns)

*

Max (ns)

Counter n Source
Pulse Width

80 MHz Source

6.2

Other Internal Source

12.5

External Source

16.0

*

The times in this table are measured at the pin of the device.

Actual performance depends on the module in use.