Interpreting the leds, Figure 44, Bip leds and indicators – Nortel Networks 8010co User Manual

Page 68: Table 4, Table 4 describ es the bip leds and indicators

Advertising
background image

68

Chapter 3 Problem solving

312755-G Rev 00

Interpreting the LEDs

All BIP LEDs and indicators are located on the front panel (

Figure 44

).

Figure 44 BIP LEDs and indicators

Table 4

describes the BIP LEDs and indicators.

Table 4 BIP LEDs and indicators

Item

Label/Icon

Type

Color/State

Description

1

Upper Shelf/
Lower Shelf

LED

Red/On steady

Circuit breaker LEDs (for upper shelf and lower
shelf power supplies)—Indicates that a circuit
breaker has tripped due to an overcurrent condition
with the associated power supply.

This fault condition also lights the (red) MAJOR fault
indicator (see MAJOR fault description in this table).

No alarm is generated when a shelf circuit breaker
is manually switched on (|) or off (O).

2

LED

Red/On steady

Shelf alarm cable fault LED—The shelf alarm
cables are missing, not secured, or the shelf alarm
jumpers are not configured properly (see

“Accessing the alarm module” on page 30

). This

fault condition also lights the MINOR fault indicator
(see Minor fault description in this table).

3

LED

Green/On steady

Shelf alarm cable validation LED —The shelf alarm
cables are properly connected to the shelves.

2

10435EB

1 = Shelf circuit breakers LEDs
2 = Shelf alarm cable fault LED
3 = Shelf alarm cable validation LED

4 = POWER indicator
5 = CRITICAL fault indicator

6 = MAJOR fault indicator
7 = MINOR fault indicator

1

POWER

CRITICAL

MAJOR

MINOR

Upper Shelf

1

2

3

1

2

3

Lower Shelf

Alarm Module

7

6

4

5

3