Corrective actions, Table 5 – Nortel Networks 8010co User Manual

Page 71

Advertising
background image

Chapter 3 Problem solving

71

Installing the Breaker Interface Panel for the Ethernet Routing Switch 8010co Chassis

Corrective actions

To resolve problems with the BIP or the 8010co chassis and components, follow
the corrective actions suggested in

Table 5

.

Table 5 Corrective actions

Symptom

Probable cause

Corrective action

The (red) shelf
alarm cable fault
LED on the BIP
front panel is on,
and the (yellow)
MINOR indicator is
on steady.

Shelf alarm cables are not
installed or installed
incorrectly.

Check to see that the shelf alarm cables are secure and
installed correctly, see

“Installing shelf alarm cables” on

page 61

.

Shelf alarm jumpers not
configured or configured
incorrectly.

Check the shelf alarm jumper settings, see

“Accessing

the alarm module” on page 30

.

The (yellow)
MINOR indicator is
on steady.

A single chassis fan tray is
faulty.

Locate and replace the faulty chassis tray, see the
appropriate product chassis installation manual.

A single power supply is
faulty.

Locate and replace the faulty power supply, see the
appropriate product chassis installation manual.

The (red) MAJOR
indicator is on
steady.

Two chassis fan trays are
faulty.

Locate and replace the faulty chassis trays.

See the appropriate product chassis installation manual,
for replacement and removal of system components.

Two power supplies are
faulty.

Locate and replace the faulty power supplies.

See the appropriate product chassis installation manual,
for replacement and removal of system components.

An overcurrent condition
has occurred with one or
more power supplies.

This fault condition causes the associated circuit
breaker(s) on the BIP front panel to trip, and also lights
the circuit breaker LED.

Locate and replace the faulty power supplies.

See the appropriate product chassis installation manual,
for replacement and removal of system components.

The master CPU has
failed and the second
(redundant) CPU has
taken over system
operations.

Locate and replace the faulty CPU.

See the appropriate product chassis installation manual,
for replacement and removal of system components.