Gpctr1_out signal, Figure 4-34. gpctr1_out signal timing, Gpctr1_up_down signal – National Instruments NI 6014 User Manual

Page 64: Gpctr1_out signal -38 gpctr1_up_down signal -38

Advertising
background image

Chapter 4

Connecting Signals

NI 6013/6014 User Manual

4-38

ni.com

Figure 4-33 shows the timing requirements for GPCTR1_GATE.

Figure 4-33. GPCTR1_GATE Signal Timing in Edge-Detection Mode

GPCTR1_OUT Signal

This signal is available only as an output on the GPCTR1_OUT pin.
GPCTR1_OUT monitors the TC device general-purpose counter 1.
You have two software-selectable output options—pulse on TC and toggle
output polarity on TC. The output polarity is software selectable for both
options. This output is set to high-impedance at startup.

Figure 4-34 shows the timing requirements for GPCTR1_OUT.

Figure 4-34. GPCTR1_OUT Signal Timing

GPCTR1_UP_DOWN Signal

This signal can be externally input on the DIO7 pin and is not available
as an output on the I/O connector. General-purpose counter 1 counts down
when this pin is at a logic low and counts up at a logic high. This input
can be disabled so that software can control the up-down functionality
and leave the DIO7 pin free for general use. Figure 4-35 shows the timing
requirements for the GATE and SOURCE input signals and the timing
specifications for the OUT output signals of the device.

Rising-Edge

Polarity

Falling-Edge

Polarity

t

w

= 10 ns minimum

t

w

Rising-Edge

Polarity

Falling-Edge

Polarity

t

w

= 10 ns minimum

t

w

Advertising
This manual is related to the following products: