Subaru Robin Power Products RG2800I User Manual

Page 20

Advertising
background image

– 17 –

4-2) AC OUTPUT MEASURING

SWITCH

LOAD

TO AC RECEPTACLE

F

A

~

V

~

Use a circuit above for measuring AC output. A hot plate or lamp with a power factor of 1.0 may be used as a

load. Adjust the load and rpm, and check that the voltage range is as specified in the following table at the

rated amperage and rated rpm.

4-3) DC OUTPUT MEASURING

To DC Terminal

SW

Load

Measurement of DC output is executed with the switch turned ON while the current is regulated at 8.3A by

adjusting the load to the generator. If the voltage is within the range from 6V to 14V, the voltage output is

normal.

NOTE : If a battery is connected as a load to the generator, the DC output voltage will increase by

approximately 1 to 2 V.

Therefore, carefully observe the electrolyte level and do not overcharge the battery.

120V / 60Hz

215-238

235-259

RG2800i
RG3200i
RG4300i

RG2800iS
RG3200iS
RG4300iS

117-130

220V / 50Hz

240V / 60Hz

Voltage range

Model

Specification

225-248

230V / 50Hz