F. installing adaptor and termination cap, Masonry factory built wood burning – Quadra-Fire QVI-35FB-S User Manual

Page 23

Advertising
background image

Quadra-Fire • QVI-35FB-S • 2178-900 Rev. B • 12/08

23

F. Installing Adaptor and Termination Cap

For installation of termination cap see minimum vent
heights for various pitched roofs (see Figure 8.5) .

To install adaptor see Figure 8.6.

Roof Pitch H (Min.) Ft.
Flat to 6/12....................1.0*
Over 6/12 to 7/12 ........1.25*
Over 7/12 to 8/12 ..........1.5*
Over 8/12 to 9/12 ..........2.0*
Over 9/12 to 10/12 ........2.5*
Over 10/12 to 11/12 ..... 3.25

Figure 8.5 Minimum Height from Roof to Lowest Discharge
Opening

* 3 foot minimum in snow regions

Roof Pitch H (Min.) Ft.
Over 11/12 to 12/12 ....... 4.0
Over 12/12 to 14/12 ....... 5.0
Over 14/12 to 16/12 ....... 6.0
Over 16/12 to 18/12 ....... 7.0
Over 18/12 to 20/12 ....... 7.5
Over 20/12 to 21/12 ....... 8.0

CLASS A PIPE

Figure 8.6

CAUTION! Risk of Cuts/Abrasions/Flying Debris.
Wear protective gloves and safety glasses during instal-
lation. Sheet metal edges are sharp.

Damper Flashing Kit (Optional)

For use with LINK-DV4-30B Liner Kit.

Note: Damper may have to be removed to use this kit.

• Run fl ex liners through 3” holes in damper fl ashing.

• Attach damper fl ashing to fi rebox roof with self tapping

screws included in kit.

Figure 8.7

To prevent odors and cold drafts, the chimney must be
sealed around the vent with non-combustible blanket in-
sulation or fi eld fabricated metal plates.

Note: The LINK-DV4-30B system REQUIRES this
insulation.

Masonry

Factory Built

Wood Burning

EXHAUST

AIR

VENT PIPE

TERMINATION

CAP

SEAL GAP

AROUND FLEX PIPE

LINK-DV30B

Installation

LINK-DV4-30B

Installation

INLET AIR

VENT PIPE

WARNING:

DO NOT BLOCK

THIS PIPE END!

Note: Untwist the pipe
while extending it, to
achieve full 30’ length.

EXHAUST

AIR

VENT PIPE

INLET AIR

VENT PIPE

Remove 18 inch x 18 inch fl ashing on cap by removing 3
screws. Connect both the LINK-ZC-ADPB to Class A Pipe
and the termination cap to the LINK-ZC-ADPB with the
self tapping screws provided.

OPTIONAL LINK-ZC-ADPB

FOR USE WITH CLASS A

WOODBURNING PIPE

OR

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT
TERMINATION CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING