Troubleshooting – Quadra-Fire QVI-35FB-S User Manual

Page 34

Advertising
background image

Quadra-Fire • QVI-35FB-S • 2178-900 Rev. B • 12/08

34

A. Standing Pilot Ignition System

13

13

Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you
do experience a problem, this troubleshooting guide will assist a qualifi ed technician in the diagnosis of a problem and the
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed technician. Contact your dealer to
arrange a service call by a qualifi ed technician.

Symptom

Possible Causes

Corrective Action

1. After repeated triggering

of the red or black piezo
ignitor button, the spark
ignitor will not light the
pilot.

A. No gas or low gas pressure.

Check the remote shut-off valves from the appliance. Usually, there
is a valve near the gas main. There can be more than one valve
between the appliance and the main.

B. No lp in tank.

Check the LP (propane) tank. You may be out of fuel.

C. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode
wire is properly connected, replace the ignitor. Verify that there is no
short in electrode wire.

D. Defective pilot or misaligned

electrode (spark at elec-
trode).

Using match, light the pilot. If the pilot lights, turn off the pilot and
trigger the piezo ignitor button again. If the pilot lights, an improper
gas/air mixture caused the bad lighting and a longer purge period is
recommended. If the pilot will not light, ensure the gap at the elec-
trode and pilot is one-eighth inch to have a strong spark. If the gap
is OK, replace the pilot.

2. The pilot will not stay lit

after carefully following
the lighting instructions.

A. Defective thermocouple.

Check that the pilot fl ame impinges on the thermocouple. Adjust the
pilot for proper fl ame impingement.

Ensure that the thermocouple connection at the gas valve is fully
inserted and tight (hand tighten plus 1/4 turn).

Verify proper voltage output from the thermocouple to the valve.
Place one millivolt meter lead wire on the thermocouple copper lead.
Place the second lead wire on the solder button on the back of the
valve (blue wire). Start the pilot and hold the valve knob in. The
millivolt reading should read 8-16 millivolts. If millivolt reading is
less than 8 millivolts, replace thermocouple.

B. Improper gas inlet pressure.

Natural gas should be 5-14 in. w.c. LP should be 10-14 in. w.c.
Verify pressure with manometer.

C. Defective valve.

If the thermocouple is producing 8-16 millivolts, replace faulty valve.

3. The pilot is burning,

there is no burner
fl ame, the valve knob is
in the ON position, and
the ON/OFF switch is in
the ON position.

A. On/off switch or wires defec-

tive.

Check the ON/OFF switch and wires for proper connections. Place
the jumper wires across the terminals at the switch. If the burner
comes on, replace the defective switch. If the switch is OK, place
the jumper wires across the switch wires at the gas valve. If the
burner comes on, the wires are faulty or connections are bad.

B. Thermopile may not be gen-

erating suffi cient millivoltage.

Check that the pilot fl ame impinges thermopile properly.

Be sure the wire connections from the thermopile at the gas valve
terminals are tight and that the thermopile is fully inserted into the
pilot bracket.

Check the thermopile with a millivolt meter. Take the reading at
TH-TP&TP terminals of the gas valve. The meter should read 350
millivolts minimum, while holding the valve knob depressed in the
pilot position, with the pilot lit, and the ON/OFF switch in the OFF
position. Replace the faulty thermopile if the reading is below the
specifi ed minimum.

With the pilot in the ON position, disconnect the thermopile leads
from the valve. Take a reading at the thermopile leads. The read-
ing should be 350 millivolts minimum. Replace the thermopile if the
reading is below the minimum.

Advertising