Castile Pellet Insert
NOTE: Check clearances carefully for this type of instal-
lation to ensure adequate room for outside air venting.
Check building codes prior to installation.
• Installation MUST comply with local, regional, state and 
national codes and regulations.
• Consult local building, fi re offi cials or authorities having
jurisdiction about restrictions, installation inspection, and 
permits.
CAUTION
NOTE: In Canada only a full reline is allowed per ULC 
S628, ORD ULC C1482-M1990.
B. Full Reline With Outside Air - Vertical
Figure 16.1
Outside Air
Termination
at
Chimney Top
(Vertical)
305mm min. 
below
305mm min. 
above
NOTE; Use metal plate around 
exhaust vent pipe and seal all 
edges with non-flammable insula-
tion such as fiberglass, mineral 
wool or ceramic.
Do not use high temperature caulk-
ing materials to seal any edge to 
prevent furture serviceability.
NOTE: In Canada this fi replace insert must be installed 
with a continous chimney liner a 6 inch (152mm) in diam-
eter extending from the fi replace insert to the top of the 
chimney. The chimney liner must conform to the Class 
3 requirments of CAN/ULC-S635, Standard for Lining 
Systems for Extising Masonry or Factory-Built Chimneys 
and Vents, or CAN/ULC-S640, Standard for Lining Sys-
tems for New Masonry Chimneys.