LAE CONTROL

SEQUENCE OF OPERATION

1. Cabinet is plugged in.

a. Display will illuminate.

b. Interior light will illuminate on glass door models only. (If lights do not come on please see

instructions on following page(s).) Solid door cabinet lights are controlled by door switch.

2. After the LAE control preprogrammed time delay of 3 minutes, the compressor and evaporator fan(s) will start if

the control is calling for cooling.

a. Control may be already pre-programmed from the factory so at the start of every compressor cycle or

during a defrost cycle, the condenser fan(s) will reverse for 30 seconds to blow dirt off the condensing
coil.

3. The LAE control will cycle the compressor but may also cycle evaporator fan(s) on and off determined by the

Set-Point and Differential temperatures. (If the Set-Point needs to be changed due to conditions please see
instructions on the following page(s).)

a. The

Set-Point is the preprogrammed temperature which shuts off the compressor.


b. The

Differential is the preprogrammed temperature that is added to the Set-Point temperature that will

start the compressor.

Example: If the Set-Point is -9°F/-23°C and the Differential is 10°F/5°C

(Set-Point) -9°F + 10 (Differential) = 1°F

Or

(Set-Point) -23°C + 5 (Differential) = -18°C

The compressor and evaporator fan(s) will cycle off -9°F/-23°C

and back on at 1°F/-18°C

4. The LAE control may be preprogrammed to initiate defrost by interval or at specific times of day. (If additional

Defrost Intervals or Cycles are needed or a Manual Defrost is required due to conditions please see instruc-
tions on the following page(s).)

a. At this time the “dEF” will appear on the display and compressor will turn off until a preprogrammed

temperature or duration is reached. During this time for freezers only, evaporator fan(s) will also

turn off and the coil heater and drain tube heaters will also be energized.


b. After the preprogrammed temperature or duration for defrost has been reached there may be a short

delay for both the compressor and evaporator fans to restart. At this time “dEF” may still appear

on the display for a short time.

True Manufacturing recommends that ONLY the Set-Point and/or

Defrost Interval may be adjusted due to certain conditions.

This sequence is NOT model specific.

If you have any questions, please contact the Technical Service Department.