E6581738

- 10 -

3.2.

STW Control Word Data

PDP003Z supports only speed control mode.

Bit Value

Name

Note

1

ON

“Switched on” condition

0

0

OFF Normal

stop.

1

No Coast Stop

All "Coast Stop (OFF2)" commands are withdrawn

1

0

Coast Stop (OFF 2)

Coast stop.

1

No Quick Stop

All "Quick Stop (OFF3)" commands are withdrawn.

2

0

Quick Stop (OFF 3)

Quick Stop

1

Enable Operation

The drive then runs-up to the setpoint.

3

0

Disable Operation

Normal stop.

1

Enable Ramp Generator

-

4

0

Reset Ramp Generator

Output of the RFG is set to 0.

1

Unfreeze Ramp Generator

-

5

0

Freeze Ramp Generator

Freeze the actual setpoint entered by the RFG *.

1

Enable Setpoint

The value selected at the input of the RFG is switched-in.

6

0

Disable Setpoint

The value selected at the input of the RFG is set to 0.

1

Fault Acknowledge

Fault reset (0 -> 1)

7

0

No meaning

-

1

JOG 1 ON **

VF-MB1/S15 drives with JOG 1 speed 1 (

c154

).

8

0

JOG 1 OFF

Jogging stop, if "JOG 1" was previously ON. Stop drive
according to VF-MB1/S15 setting parameter.

1

JOG 2 ON **

VF-MB1/S15 drives with JOG 2 speed 2 (

c155

).

9

0

JOG 2 OFF

Jogging stop, if "JOG 2" was previously ON. Stop drive
according to VF-MB1/S15 setting parameter.

1

Control By PLC

The control word and main setpoint are activated.

10

0

No Control By PLC

The control word and main setpoint are inactivated.

11 ---

Device-specification

(Reserved.)

1

Net Control

PDP003Z control is enabled.

12

0

Local Control

PDP003Z control is disabled.

1

Net Reference

PDP003Z reference is enabled.

13

0

Local Reference

PDP003Z reference is disabled.

14 ---

Device-specification

(Reserved.)

15 ---

Device-specification

(Reserved.)

* RFG: Ramp Function Generator
** Operation is enabled, drive is in standstill and STW1 bit 4, 5, 6 = 0.