Access to VF-MB1/S15 parameter

When access to VF-MB1/S15 parameter, set “1” to the PNU. The communication number
of the drive parameter is set to the subindex IND.
Refer to the drive instruction manual about the communication number and unit.
* This procedure changes the value of VF-MB1/S15 EEPROM.

3.7.1.

Examples of reading or changing VF-MB1/S15 parameter

3.7.1.1. Example 1. Reading the basic parameter (

cmod

(command mode selection))


AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0003 (

cmod

communication number)


PKE

0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1

6 0 0 1


Requirement

PKW PZD
PKE IND PWE

60 01 00 03

00 00 00 00 ・・・

・・・


Response (Value: 0x0001 = Operation panel))

40 01 00 03

00 00 00 01 ・・・

・・・


3.7.1.2. Example 2. Reading the extended parameter (

f219

(VIC input point 2 frequency))


AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0219 (

f219

communication number)


PKE

0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1

6 0 0 1


Requirement

PKW PZD
PKE IND PWE

60 01 02 19

00 00 00 00 ・・・

・・・


Response (Value: 0x1770 (= 6000 -> 60.00Hz *))

40 01 02 19

00 00 17 70 ・・・

・・・


* “0x1770” as reading value of “VIC input point 2 frequency” is

0x1770 = 6000 (decimal number)

Since the unit of “VIC input point 2 frequency” is 0.01Hz, set the following value.

6000×0.01 = 60.00Hz