Access to the profibus parameter – Toshiba Tosvert VF-MB1/S15 User Manual

Page 17

Advertising
background image

E6581738

- 15 -

3.5.

Access to the PROFIBUS parameter

In the cyclic PROFIBUS-DP communication, the parameter data is transferred via Telegram
100, 101. If the requirement is not executed, the cause is distinguished by octet 7 and 8.

PKW

(Parameter ID/value)

PZD

Process data (cyclically)

PKE IND

PWE

PZD1

STW
ZSW

PZD2

HSW

HIW

Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Octet 6 Octet 7 Octet 8

PKE (Parameter ID)

15 14

13 12 11

10 9 8 7 6 5 4 3 2 1 0



AK (Request from Master to PDP003Z)

Request ID

Function

Note

0 No

task

1

Request parameter value

for PNU access

2

Change parameter value (word)

for PNU access

6

Request parameter value (array)

for PNU access, VF-MB1/S15 parameter
access

7

Change parameter value (array)

for PNU access, VF-MB1/S15 parameter
access


AK (Response from PDP003Z to Master)

Response ID

Function

0 No

response

1

Transfer parameter value (word)

4

Transfer parameter value (array)

7

Task can not be executed, followed by error number

0 = Illegal parameter number
1 = Parameter value cannot be changed
2 = Lower or upper limit violated
3 = Erroneous sub index

11 = No parameter change rights
17 = Task cannot be executed due to operating status

(e.g. parameter is currently read-only)

18 = Other error

102 = Request not supported


SPM: always 0.

AK

(Task ID/Response ID)

PNU

(Parameter number)

SPM