Toshiba Tosvert VF-MB1/S15 User Manual

Page 21

Advertising
background image

E6581738

- 19 -

3.7.1.3. Example 3. Reading the status monitor parameter (

fe02

(The operation frequency))


AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0xFE02(fe02 communication number)

PKE

0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1

6 0 0 1


Requirement

PKW PZD
PKE IND PWE

60 01 FE 02

00 00 00 00 ・・・

・・・


Response (Value: 0x03E8 (= 1000 -> 10.00Hz))

40 01 FE 02

00 00 03 E8 ・・・

・・・


* The status monitor parameter can not be changed.

3.7.1.4. Example 4. Changing the basic parameter (

acc

(acceleration time))


AK = 7 (Change parameter value (array))
SPM = 0
PNU = 1
IND = 0x0009 (

acc

communication number)


PKE

0 1 1 1 0 0 0 0 0 0 0 0 0 0 0 1

7 0 0 1


Requirement (

acc

= 7.0 sec. -> 70 (= 0x0046) *)

PKW PZD
PKE IND PWE

70 01 00 09

00 00 00 46 ・・・

・・・


Response

40 01 00 09

00 00 00 46 ・・・

・・・


* When the “Acceleration time” is set to 7.0 sec., set the following value.

(The unit of the “Acceleration time” is according to the parameter

f519

.)

7.0/0.1 = 70 = 0x0046 (hexadecimal number)

Notes

When the control power is shut off by the instantaneous power failure,

communication will be unavailable for a while.

The Life of EEPROM is approximately 100,000 times. Avoid writing a command more

than 100,000 times to the same parameter of the drive and the communication board.