How to use – Toshiba Tosvert VF-MB1/S15 User Manual
Page 23

E6581738
- 21 -
4.1.
How to use
The purposes are adjustment by real time command transmission, and the monitor of an
operation state by using cyclic communication of PROFIBUS.
Example 1: Command transmitting
When you want to set "0xC400" to parameter fa06, set “1 (fa06)” to parameter
c001
.
And Since 0 and 1 byte of the PZD1 supports the parameter
c001
, if "0xC400" is set up
here, "0xC400" will be set as
fa06
.
Example 2: State monitoring
When you want to monitor the output current, set “3 (FD03)” to parameter
c021
.
The value of the parameter
fd03
specified as 0 and1 byte of the PZD1 with the
parameter
c021
is inputted.
VF-MB1
PDP003Z
"0xC400" is set as parameter fa06
PZD1 PZD2 PZD3
C4
00 ... ... ...
...
PROFIBUS Master
Parameter Value
c001
1 (FA06)
c002
...
c003
...
... ...
Parameter Value
c021
3 (FD03)
c022
...
c023
...
...
...
The value of a parameter fd03 is outputted.
VF-MB1
PDP003Z
PZD1 PZD2 PZD3
xx
xx ... ... ...
...
PROFIBUS Master