Zsw status word data – Toshiba Tosvert VF-MB1/S15 User Manual

Page 13

Advertising
background image

E6581738

- 11 -

3.3.

ZSW Status Word Data

Bit Valure

Name

Note

1

Ready To Switch-on

Power supply is switched on

0

0

Not Ready To Switch-on

-

1

Ready To Operate

Refer to control word, bit 1.

1

0

Not Ready To Operate

-

1

Operation Enabled

Drive follows setpoint.
(Refer to control word 1, bit 3)

2

0

Operation Disabled

-

1

Fault Present

VF-MB1/S15 tripped.

3

0

No Fault

VF-MB1/S15 is not tripped.

1

Coast Stop Not Activated

-

4

0

Coast Stop Activated (OFF 2) "Coast Stop (OFF 2)" command is present.

1

Quick Stop Not Activated

-

5

0

Quick Stop Activated (OFF 3) "Quick Stop (OFF 3)" command is present

1

Switching On Inhibited

Control word bit1 or 2 is set to 0

or fault trip has been acknowledged.

6

0

Switching On Not Inhibited

-

1

Warning Present

Drive still operational: Alarm in service parameter: No
acknowledgement.

7

0

No Warning

Alarm not present or alarm has disappeared again

1

Speed Error

Within Tolerance Range

8

0

Speed Error

Out Of Tolerance Range

Refer to section 3.3.1.

1

Control Requested

VF-MB1/S15 is controlled by PROFIBUS master.

9

0

No Control Requested

VF-MB1/S15 is controlled by another interface.

1

f Or n Reached Or Exceeded

Actual value ≥ Comparison value (setpoint)

10

0

f Or n Not Reached

-

11 ----

Device-specification

(Reserved.)

12 ----

Device-specification

(Reserved.)

13 ----

Device-specification

(Reserved.)

14 ----

Device-specification

(Reserved.)

15 ----

Device-specification

(Reserved.)

Advertising