4.2.1.

fa06

(Communication command1)

bit Function

0

1

Note

0

Preset speed
operation frequencies
1

1

Preset speed
operation frequencies
2

2

Preset speed
operation frequencies
3

3

Preset speed
operation frequencies
4

Preset speed operation is disabled
or preset speed operation
frequencies (1-15) are set by
specifying bits for preset speed
operation frequencies 1-4.
(0000: Preset speed operation OFF,
001-1111: Setting of preset speed
operation frequencies (1-15)

4

Motor selection (1 or 2)
(THR 2 selection)

Motor 1

(THR 1)

Motor 2

(THR 2)

THR 1: pt = setting value, thr
THR 2: pt = 0, f170,

f171

, f172, f173

5

PI D control

Normal operation

PI D off

-

6

Acceleration/decele-
ration pattern selection
(1 or 2)
(AD2 selection)

Acceleration/decel

eration pattern 1

(AD1)

Acceleration/dec

eleration pattern

2

(AD2)

AD1: acc, dec
AD2: f500, f501

7 DC

braking

OFF

Forced DC

braking

-

8

Jog run

OFF

Jog run

-

9

Forward/reverse run
selection

Forward run

Reverse run

-

10 Run/stop

Stop

Run

-

11

Coast stop command

Standby

Cost stop

-

12

Emergency stop

OFF

Emergency stop Always enable, "E" trip

13

Fault reset

OFF

Reset

No data is returned from the drive

14

Frequency priority
selection

OFF Enabled

Enabled regardless of the setting
of fmod

15

Command priority
selection

OFF Enabled

Enabled regardless of the setting
of cmod

* VF-S15:When 14(sr0) is set to fmod, preset speed operation frequency 0 is selected.