Example 3. read the vf-mb1/s15 parameter, Read response data table (positive) – Toshiba Tosvert VF-MB1/S15 User Manual

Page 35

Advertising
background image

E6581738

- 33 -

6.3.

Example 3. Read the VF-MB1/S15 parameter

When access to VF-MB1/S15 parameter, set “1000” to the PNU.

6.3.1.

Write Request data table (Read

fd04

(Input voltage))

Field Description

Value

Header DU0

Function number

0x5F

Header DU1

Slot number (0)

0x00

Header DU2

Index (47)

0x2F

Header DU3

Length

0x0A

Request Header (Byte 1)

Request Reference

0x01

Request Header (Byte 2)

Request ID (0x01: Request) *

0x01

Request Header (Byte 3)

Axis

0x01

Request Header (Byte 4)

Number of Parameters

0x01

Parameter Address (Byte 1)

Attribute

0x10

Parameter Address (Byte 2)

Number of Elements

0x01

Parameter Address (Byte 3)

Parameter number, High byte **

0x03

Parameter Address (Byte 4)

Parameter number, Low byte **

0xE8

Parameter Address (Byte 5)

VF-MB1/S15 Parameter number, High byte

0xFD

Parameter Address (Byte 6)

VF-MB1/S15 Parameter number, Low byte

0x04

* Refer to Appendix.
** Parameter number is fixed to 0x03E8 (1000) for accessing to VF-MB1/S15 parameter.


6.3.2.

Read Response data table (positive)

Field Description

Value

Header DU0

Function number

0x5E

Header DU1

Slot number (0)

0x00

Header DU2

Index (47)

0x2F

Header DU3

Length

0x08

Request Header (Byte 1)

Request Reference (mirrored)

0x01

Request Header (Byte 2)

Response ID *

0x01

Request Header (Byte 3)

Axis (mirrored)

0x01

Request Header (Byte 4)

Number of Parameters

0x01

Parameter Value (Byte 1)

Format *

0x42

Parameter Value (Byte 2)

Number of Values

0x01

Parameter Value (Byte 3)

Values, High byte

0x31

**

Parameter Value (Byte 4)

Values, High byte

0xEC

**

* Refer to Appendix.
** Value 0x31EC is "12780" in decimal. This means "127.80 (%)".