Pre-installation considerations installation, Split-apart unit assembly – Trane IntelliPak SCWG 020 User Manual

Page 14

Advertising
background image

14

SCXG-SVX01B-EN

Split-Apart Unit Assembly

1. Ensure the tagging information on the

fan section nameplate matches that on
the compressor nameplate.

2. Remove the connector brackets holding

the the sheet metal shipping cover on
compressor section. Retain brackets
and screws.

3. Remove shipping cover from the

compressor section and verify the ship-
with packge contains:

• suction and discharge line couplings
• insulation
• sheet metal screws
4. Lift fan section onto the compressor

section using the rigging method in
Figure I-PC-8 on page 13.

5. Remove skid from the fan section,

placing the fan section onto the
compressor section. Reference Figure I-
PC-9 on page 15.

6. Install the connection brackets with the

sheet metal screws (referenced in step
2) on all sides of the unit. Reference
Detail “A” in Figure I-PC-9.

7. Remove the unit panels labeled RU and

RL in Figure I-PC-10 on page 15. To
remove panels, first remove the four
shipping screws located in the corner of
each panel. Next, turn the remaining

1

/

4

turn fasteners to the unlatch position.
The panel is supported by a “lip”
channel. So, lift the panel up and off the
unit to remove it. See Detail “A”in Figure
I-PC-9 on page 15.

8. Connect the drain hose to the drainpan

outlet fitting and secure it with the drain
hose clamp provided.

9. Circulate nitrogen thoughout

refrigerant circuits.

10. Unbraze and remove the caps on the

discharge and suction lines in both the
compressor and fan sections.

11. Install and braze discharge and suction

line couplings.

12. Insulate discharge and suction lines

with the insulation provided.

13. Remove panel FLR and open the

bottom control panel door, FLL. Pull the
fan motor leads (coiled in the fan
section) through the knockout in the
bottom of the fan section to the control
panel. Ensure that the bushing is
installed in the hole to prevent the
wires from chafing. Refer to the unit
wiring diagrams to connect the fan
motor leads properly and ensure
correct phase sequencing.

IntelliPak Units (UCM) Only
14. Remove panels FML, FMM, and FMR.
15. Pull the circular plug connector (CPC)

from the compressor section through
the knockouts into the fan section.
Install the bushings (provided on the
wiring harnesses) in the knockouts.

16. Using the CPC wiring diagram,

connect the male CPC to the female
CPC in the top control panel.

17. If the unit has the mixed air

temperature option, route the capillary
tube on back of the filter rack.

Units with Thermostat Only
18. Remove panel FMR. See Note 1 on

Figure I-PC-10.

19. Pull frost protection wires from the

bottom control panel throughknockouts
in bottom of fan section. Route wires to
the appropriate frost protection
switches on the evaporator coil.
Reference the unit wiring diagrams to
connect frost protection wiring
connectors.

Air-Cooled Units Only:
20. Route the refrigerant circuit wires for

circuits 1 and 2 from the bottom control
panel through the knockouts to the
solenoid valves. The solenoid valves
are located in the liquid refrigerant
lines on the right-hand side of the unit.
Refer to the unit wiring diagrams to
make splice connections.

Pre-Installation
Considerations

Installation

Advertising