Pre-Startup
Requirements

Mounting the Remote Human
Interface (RHI) Panel

The installer must provide all mounting
hardware such as; hand tools, electrical
boxes, conduit, screws, etc. Refer to
Figure I-PR-32 on page 60 for the
mounting hole and knockout locations.

Procedure
Follow the procedure below for
mounting the remote HI panel on a 4” by
4” electrical junction box. Place the
microprocessor in a clean dry location
during the enclosure mounting
procedures to prevent damage.

1. Mount an electrical junction box in the

wall so that the front edge of the box
will be flush with the finished wall
surface.

2. Prior to mounting the panel, the

microprocessor module must be
carefully removed from the enclosure.
To remove the module:

a. Lay the remote panel face up on a flat

surface and remove the locking screw
from the right hand bottom end of the
panel.

b. Remove the recessed hinge screw

from the left hand bottom end of the
panel.

c. Unlatch the door of the enclosure as if

to open it, and slide the left hand side of
the door upward away from the hinge.
Lay it aside.

d. With the key pad visible, remove the

two (2) screws located on the right
hand side of the key pad.

e. Carefully slide the key pad plate

upward from the bottom, releasing the
extruded hinge pin from its socket at
the top.

f. Set the microprocessor aside until

mounting is complete.

3. Remove the junction box knockout in

the back of the enclosure.

Note: The top of the enclosure is marked
“TOP.”

4. With the enclosure in the correct

position; align the mounting holes
around the knockout in the enclosure
with the screw holes in the electrical
handy box and secure with the
appropriate screws.

5. Replace the microprocessor within the

enclosure as follows:

a. Verify that the terminal block jumpers

are connected properly.

b. Slide the extruded hinge pin at the top

left of the key pad plate into the hole
located at the top left hand side of the
enclosure.

c. Slide the bottom of the plate into place,

aligning the two (2) clearance holes
with the screw holes on the right. Install
the screws but do not tighten at this
time.

Note: If the two screws are not installed as
called out in the previous step, hold
against the key pad plate while installing
the door in the next step, to prevent it from
falling out.

d. Slide the extruded hinge pin at the top

left of the door into the hole located
under the bottom left side of the display.

e. Install and tighten the hinge screw

located at the bottom left side of the
enclosure.

Wall Mounting the RHI Panel
1. Prior to mounting the panel, the

microprocessor module must be
removed from the enclosure. Complete
step 2 in the previous discussion,
“Mounting on a 4 in. x 4 in. Electrical
Box,” before proceeding.

2. With the microprocessor removed,

refer to Figure I-PR-31 for the location of
the mounting holes to be used for wall
mounting.

3. Place the enclosure against the

mounting surface and mark the
mounting holes.

Note: The top of the enclosure is marked
with “TOP.”

4. With the enclosure in the correct

position, remove the enclosure and
drill the necessary holes in the surface
for the appropriate fasteners, (plastic
anchors, molly bolts, screws, etc.)

5. Remove the necessary knockouts for

the wire or conduit entry before
mounting the panel.

6. Place the enclosure back onto the

surface and secure it with the
appropriate screws.

7. Follow step 5 in the previous section,

“Mounting on a 4” by 4” Electrical
Box,” to replace the microprocessor
within the enclosure.

Installation

Advertising