Owner general information – Trane IntelliPak SCWG 020 User Manual

Page 81

Advertising
background image

SCXG-SVX01B-EN

81

Figure O-GI-2. Velocity Pressure Trans-
ducer/Solenoid Assembly.

• VO relay – energized
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open

PURGE sequence “D”
This sequence could be used for purging
the air out of a building before coming out
of unoccupied mode of operation on VAV
units. Also, it can be used to purge smoke
or stale air.
• Supply fan – on
• Supply fan VFD – on (60 Hz)

(if equipped)

• Inlet guide vanes/VAV boxes – Open

(if equipped)

• Outside air damper – Open
• Heat – all stages – Off, Modulating heat

output at 0 vdc

• Occupied/unoccupied output – Energized
• VO relay – Energized
• Exhaust fan (field-installed) - On
• Exhaust damper (field-installed) - Open

PURGE with duct pressure control “E”
This sequence can be used when supply
air control is required for smoke control.
• Supply fan – on
• Supply fan VFD – on (if equipped)
• Inlet guide vanes – controlled by supply

air pressure control function with
supply air pressure high limit disabled

• Outside air dampers – open
• Heat – all stages – off, hydronic heat

output at 0 vdc

• Occupied/unoccupied output – energized
• VO relay – energized
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open

Note: Each system (cooling, exhaust,
supply air, etc.) within the unit can be
redefined in the field for each of the five
sequences, if required. Also the definitions
of any or all of the five sequences may be
locked into the software by simple key
strokes at the human interface panel. Once
locked into the software, the sequences
cannot be changed.

Trane Communications
Interface Module (TCI) - Option
used with Trane ICS

TM

The Trane communication interface
module allows external setpoints for
most of the unit functions to be
communicated to the unit's UCM network
via a Trane ICS

TM

systems. DIP switch

settings on the TCI module for this

Owner

General
Information

application are; switch 1 “off,” 2 “on,” and
3 “off.”

Exhaust/Comparative
Enthalpy Module (ECEM) - On
Units with Comparative
Enthalpy Option

The exhaust/comparative enthalpy
module receives information from the
return air humidity sensor, and the RTM
outside air temperature sensor and
outside air humidity sensor, the outside
air humidity sensor and temperature
sensor to utilize the lowest possible
enthalpy level when considering
economizer operation. In addition, it
receives space pressure information to
maintain the space pressure within the
setpoint control band. Refer to the Figure
O-GI-1 for humidity vs. voltage values.

Ventilation Control Module
(VCM) - Available only with
Traq™ Damper Option

The ventilation control module (VCM) is
located in the airside economizer section
of the unit and linked to the unit’s UCM
network. Using a velocity pressure
transducer/solenoid (pressure sensing
ring) in the fresh air section allows the
VCM to monitor and control fresh air
entering the unit to a minimum airflow
setpoint. See Figure O-GI-2 for a detail
view of the velocity pressure transducer/
solenoid assembly.

An optional temperature sensor can be
connected to the VCM to enable control
of a field installed fresh air preheater.

Also, a field-provided CO

2

sensor can be

connected to the VCM to control CO

2

reset. The reset function adjusts the
minimum cfm upward as the CO

2

concentrations increase. The maximum
effective (reset) setpoint value for fresh
air entering the unit is limited to the
system’s operating cfm. Table O-GI-5 lists
the minimum outside air cfm vs. input
voltage.

Table O-GI-5. Minimum Outside Air
Setpoint w/VCM Module and Traq™
Sensing.

Unit

Input Volts

CFM

SXWG 20

0.5 - 4.5 vdc

6,350-8,500

SXWG 25

0.5 - 4.5 vdc

7,250-10,625

SXWG 30

0.5 - 4.5 vdc

7,250-12,750

SXWG 35

0.5 - 4.5 vdc

7,250-14,875

SXRG 20

0.5 - 4.5 vdc

7,250-8,500

SXRG 25

0.5 - 4.5 vdc

7,250-10,625

SXRG 32

0.5 - 4.5 vdc

7,250-13,600

Figure O-GI-1. ECEM Relative Humidity vs.
Voltage.

Advertising