Programming installation, Intelligent copy – Trane IntelliPak SCWG 020 User Manual

Page 70

Advertising
background image

70

SCXG-SVX01B-EN

Programming

Installation

Table I-P-2. Zone Sensor BAYSENS020 Option Menu Settings.

Option #

Description

Value

Factory Setting

1

Morning Warmup

0 = Disabled

0

1 = Enabled

2

Economizer minimum

0 = Disabled

1

Position override

1 = Enabled

3

Temperature Scale

0 = Fahrenheit

0

1 = Enabled

4

Heat Installed

0 = No

0

1 = Yes

5

Time Clock

0 = 12 hours

0

1 = 24 hours

6

Hydronic Heat

0 = No

0

1 = Yes

7

Daytime Warmup

0 = Disabled

0

1 = Enabled

8

Programmable Days/Week

0 = 7 days (M,T,W,T,F,S,S)

0

1 = 3 days (M-F, S, S)

2 = 2 days (M-F, S,S)

9

Programmable Periods/Day

2,3,4

4

10

Remote Sensor Installed

0 = No

0

1 = Yes

11

Check Filter Interval

0 = Disabled

350

3000 to 50 in 50 hour

increments

12

Display Zone Temperature

0 = No

1

1 = Yes

13

Keypad Lockout Enabled

0 = Disabled

1

1 = Enabled

14

Initial Time Setting in Temporary

1,2,3,4,5

3

Override Mode (hrs.)

15

Buzzer Options

0 = Key Press only

1

1 = Key Press & Check filter
2 = Key Press, Check Filter,

and System Failures

16

Zone Temperature Calibration

Displays current temp.

0 offset

with any offsets

17

Default Cooling Setpoint

45 to 98 F (unoccupied)

74 F

18

Default Heating Setpoint

43 to 96 F (unoccupied)

68 F

19

Default Supply Air Cool

40 to 80 F (occupied)

55 F

20

Default Supply Air Heat

60 to 160 F

100 F

21

Default Warmup

50 to 90 F (occupied)

68

22

Minimum Cooling Setpoint

45 to 98 F

45 F

23

Maximum Heating Setpoint

43 to 96 F

96 F

24

Minimum Supply Air Cool

40 to 80 F (occupied)

40 F

25

Maximum Supply Air Heat

60 to 160 F

160 F

26

Maximum Warmup

50 to 90 F

90 F

Note: On both programmable zone sensor
options, changing either option 9 or 10 will
erase the current program. To avoid
reprogramming, set options 9 and 10
before programming.

Intelligent Copy

Note: Once you have used Intelligent
Copy, you cannot use it again until you
ERASE all weekday and weekend time
periods by pressing ERASE for 5 seconds.

If your heating and cooling requirements
are the same for each day of the week,
and for each day of the weekend, your
ZSM is designed to employ Intelligent
Copy.

To program the five weekdays, Monday
through Friday, program only one
weekday. Likewise, to program the
weekend, Saturday and Sunday, pro-
gram only one day. After programming
one weekday and/or one weekend day,
Intelligent Copy automatically copies your
program to the other days.

Using Intelligent Copy:
1) Be sure to select the seven day

programming format in the Options
Menu. See Tables I-P-1 and I-P-2.

2) Be sure the entire program is blank.
3) Go to the program menu.
4) Enter your setpoint parameters.

Intelligent Copy will automatically copy
these parameters to the other
weekdays.

5) Depress the DAY pushbutton until a

weekend day icon appears.

6) Enter setpoint parameters. Intelligent

Copy will automatically copy these
parameters to the other weekend day.

Remote Panel Indicator Signals From
UCM to ZSM
The unit control module (UCM) can send
four signals to the ZSM.

• Heat

• Cool

• On

• Service

Each of these four signals have three
different conditions. See Table I-P-3.
• Off
• On
• Flashing

Table I-P-3. UCM Signal Conditions.

Signal

Condition

Heat

On

FlashingHEAT is ON and indicated by a solid HEAT icon in the

Display. Failure in the cooling system indicated by a flashing COOL

FAIL icon.

Cool

On

FlashingCOOLING is ON and indicated by a solid COOL icon in the

Display. Failure in the cooling system indicated by a flashing
COOL FAIL icon.

On

Off

FlashingSystem is OFF and indicated by a solid colon on the time of

On

day display. System is ON and indicated by a flashing colon on
the time of day display. System is in TEST mode and indicated by a
flashing TEST icon.

Service

Flashing

ON System requires service and is indicated by a solid SERVICE
icon. There is a FAN failure indicated by a flashing SERVICE icon.

Note: There is no indication for a signal in the OFF condition. If Option 16 is set to “2,” any flashing signals will
also give audible buzzer indication