Pre-Startup
Requirements

Installation

Remote Mounted Thermostat
Option

Mount the thermostat in the largest
space occupied by the most people for
the best average temperature sensing.
The thermostat should be mounted about
5 feet from the floor in contact with freely
circulating air, but not with major drafts.

Avoid the following areas:
• Behind doors or in corners where ther is

no free circulation.

• Locations where the sun’s rays or

infrared radiation from appliances or
fireplaces may affect thermostat
operation.

• Surfaces subject to vibration.
• On walls that contact outside air.
• Adjacent to or in line with conditioned air

discharge grilles or doorways.

Remote Mounted Thermostat Wiring
After the thermostat is mounted, wire the
thermostat back to the unit control panel
according to the correct diagram shown
on inside of panel door.

The total resistance of the thermostat and
the control wiring to each terminal must

not exceed 1 ohm. Table I-PR-6 provides
recommended wire sizes for length of
run.

Wiring the Remote Air-cooled CCRC and
SCRG
The SCRG/SIRG air-cooled condenser
should be wired to the control panel of
the SCRG/SIRG unit to ensure proper
system operation. Reference unit wiring
diagrams for correct terminal locations.
Table I-PR-3 provides recommended
wires sizes for length of run.

Table I-PR-6. Control Wire Size and Maxi-
mum Length

Wire Gauge

Max. Wire Length

22

30 ft.

20

50 ft.

18

75 ft.

16

125 ft.

14

200 ft.