Table O-GI-6. GBAS Analog Input Setpoints

Control Parameter

Signal Range

Setpoint Range

Occupied Zone Cooling Setpoint

0.5 to 4.5 vdc

50 to 90 F

(CV units only)
Unoccupied Zone Cooling Setpoint

0.5 to 4.5 vdc

50 to 90 F

(CV and VAV)
Occupied Zone Heating Setpoint

0.5 to 4.5 vdc

50 to 90 F

(CV units only)
Unoccupied Zone Heating Setpoint

0.5 to 4.5 vdc

50 to 90 F

(CV and VAV)
Supply Air Cooling Setpoint

0.5 to 4.5 vdc

40 to 90 F

(VAV units only)
Supply Air Hydronic Heating Setpoint

0.5 to 4.5 vdc

40 to 180 F

(VAV units only)

Space Static Pressure Setpoint

0.5 to 4.5 vdc

0.03 to 0.30 IWC

Supply Air Pressure Setpoint

0.5 to 4.5 vdc

0.0 to 5.0 IWC

(VAV units only)

Note: 1. Input voltages less than 0.5 vdc are considered as 0.5 vdc input signal is lost, the setpoint will
“clamp” to the low end of the setpoint scale. No diagnostic will result from this condition.
2. Input voltages greater than 4.5 vdc are considered to be 4.5 vdc.
3. The actual measured voltage is displayed at the HI.

Table O-GI-7. GBAS Input Voltage Corresponding Setpoints

Volts Temp.

Volts

Temp.

Volts

Temp

Volts

Temp

(F)

(F)

(F)

(F)

0.5

50

1.6

60

2.6

70

2.7

80

0.6

51

1.7

61

2.7

71

2.8

81

0.7

52

1.8

62

2.8

72

2.9

82

0.8

53

1.9

63

2.9

73

3.0

83

0.9

54

2.0

64

3.0

74

3.1

84

1.0

55

2.1

65

3.1

75

3.2

85

1.1

56

2.2

66

3.2

76

3.3

86

1.2

57

2.3

67

3.3

77

3.4

87

1.3

58

2.4

68

3.4

78

3.5

88

1.5

59

2.5

69

3.5

79

3.6

89

Owner

General
Information

Advertising