15 indoor unit outdoor unit – Toshiba RAV-SM1101BT-E User Manual

Page 17

Advertising
background image

15

Indoor unit

Outdoor unit

Outer diameter of refrigerant pipe

Gas side ØA

Liquid side ØB

15.9mm

9.5mm

Distributor
(Strainer incorporated)

TCJ sensor

Air heat exchanger

Strainer

Strainer

TC sensor

Strainer

Refrigerant pipe
at gas side
Outer dia. ØA

Refrigerant pipe
at liquid side
Outer dia. ØB

Ball valve

Outer dia. ØA

Packed valve

Outer dia. ØB

Max.
50m

TS sensor

Check joint

TD sensor

TO sensor

TE sensor

Distributor

4-way valve

(STF-0213Z)

Ш25 Ч L210

Ш25 Ч L180

Rotary

compressor

(DA220A2F – 20L)

Accumulator

(2500cc)

Heat exchanger Ø8
1 row 52 stages
FP1.3 flat fin

PMV
(UKV-25D22)

R410A 2.1kg

Cooling
Heating

Muffler

RAV-SM1001BT-E

Standard

Cooling

Overload

Low load

Standard

Heating

Overload

Low load

Pressure

(MPa)

Pd

Ps

3.3

0.9

3.0

1.0

1.0

0.8

2.5

0.6

3.3

1.1

1.8

0.2

Pipe surface temperature (°C)

Discharge

Suction

Indoor heat

Outdoor heat

exchanger

exchanger

(TD)

(TS)

(TC)

(TE)

88

10

8

38

88

14

14

46

30

8

8

3

90

4

50

2

83

17

54

13

80

–23

29

–20

Compressor

revolutions per

second (rps)

*

92

74

27

86

52

100

Indoor

fan

HIGH

HIGH

LOW

HIGH

LOW

HIGH

Indoor/Outdoor

temp. conditions

(DB/WB) (°C)

Indoor

Outdoor

27/19

35/–

32/24

43/–

18/15.5

–5/–

20/–

7/6

30.–

24/18

15/–

–20/

(70%)

*

4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.